2017-01-26 15:54:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010482
 ADD: 625 N. FLAGLER DR. SUITE # 200
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-615-3903
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 26/ 2017
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET A0.02 SEE 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDING/ MINIMUM
 TYPE OF CONSTRUCTION SHALL BE DETERMINED (TABLE 503 OF
 THE 2014 FBC-B).
  
 2) SHEET A1.12 THE FLOOR PLAN DIMENSION SHEET FOR THE
 RESTROOMS 238 AND 257 THE PLANS DO NOT HAVE THE
 DIMENSION FRONT TO BACK FOR CONSTRUCTION. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A4.21 THERE ARE VARIOUS ELEVATIONS OR VIEWS OF
 THE FRONT COUNTER WITH THE TRANSACTION COUNTER SURFACE
 AT AN ELEVATION OF 3 FT. 6 INCHES. 2014
 FBC-ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) SHEET A4.2.2 DETAILS 3 & 4 BOTH SHOW A CUT SECTION
 THROUGH A LAV AND MIRROR ABOVE, DETAIL # 6/ A5.51.
 DISCREPANCY IN PLANS, NOT THE CORRECT DETAIL.
 107.2.1.3. ADDITIONAL INFORMATION REQUIRED.
 2014 FBC-ACCESS. CODE 603.3 40 INCHES TO THE BOTTOM
 EDGE OF THE REFLECTIVE SURFACE.
  
 5) SHEET A4.22 SHOW WALL TILE INSTALLED IN ALL WET
 AREAS. SHEET A0.15 IN ALL WET AREAS THE SCHEDULE
 INDICATES A TILE FOR THE FINISH WALL AND WALL MATERIAL
 TO BE GYPSUM. PLEASE REVIEW SECTIONS 2509.2 BASE FOR
 TILE & 2509.3 LIMITATIONS OF WATER RESISTANT GYPSUM.
 2014 FBC-B.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved