2017-01-23 16:30:03 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE 2010 |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. SHEET C01 STATES THAT "WINDLOADS ARE PER ASCE 7-10" |
| AND ALSO STATES UNDER "WINDOLOAD" PER ASCE 7-05. |
| |
| SEE FBC 1603.1.4 REGARDING WIND INFORMATION REQUIRED ON |
| CONSTRUCTION DOCUMENTS AND REVISE TO INCLUDE. SEE ALSO |
| CHAPTER 35 REGARDING VERSION OF ASCE 7 AND REVISE |
| ACCORDINGLY. |
| |
| SPECIFICALLY, THE WIND SPEED, RISK CATEGORY, AND |
| EXPOSURE CLASSIFICATION IS LACKING. |
| |
| 2. THE WEBSITE (WWW.MYFLORIDALICENSE.COM) DOES NOT SHOW |
| THAT YIPING WANG, PE HAS TAKEN AN ADVANCED FBC COURSE |
| AS REQUIRED BY FLORIDA STATUTE 471.0195. THIS ISSUE |
| WILL NOT PREVENT THIS SUBMITTAL FROM PASSING PLAN |
| REVIEW, BUT FLORIDA STATUTE REQUIRES THAT FBPE IS |
| INFORMED. PLEASE TAKE THE COURSE AND HAVE THE WEBSITE |
| UPDATED. EVIDENCE THAT THE COURSE HAS BEEN TAKEN AND |
| SUBMITTED TO FBPE CAN BE FOUND UNDER "SPECIAL |
| QUALIFICATIONS", MYFLORIDALICENSE.COM. |
| |
| THIS IS NOT REQUIRED FOR THIS SUBMITTAL TO PASS PLAN |
| REVIEW. HOWEVER, IF THE WEBSITE IS NOT UPDATED AT TIME |
| OF SECOND REVIEW, FBPE WILL BE NOTIFIED AS PER FS |
| 471.0195. |
| |
| 3. SOME SECTION AND DETAIL MARKERS APPEAR AS SOLID |
| BLACK CIRCLES ON SOME PAGES; FOR INSTANCE, SEE E02, |
| E04. IF THIS IS HOW THEY ARE INTENDED TO APPEAR, PLEASE |
| CLARIFY PURPOSE, FBC 107. |
| |
| 4. THE DESIGN PROFESSIONAL'S REVIEW LETTER REFERS TO |
| CALCULATIONS, AND THE DOCUMENT NAME INCLUDES THE WORD |
| "CALCS", AND SHEET C01 REFERS TO STRUCTURAL |
| CALCULATIONS, BUT NO CALCULATIONS WERE PROVIDED; PLEASE |
| PROVIDE, FBC 1609. |
| |
| 5. THE CERTIFICATE OF AUTHORIZATION NUMBER FOR THE FIRM |
| IS ILLEGIBLE AS IT IS LOCATED BELOW A DIGITAL IMAGE OF |
| THE SIGNATURE AND SEAL; **FOR ALL SHEETS WHICH ARE |
| REVISED, PLEASE RE-LOCATE THE LICENSE INFORMATION SO IT |
| IS LEGIBLE**, FS471. IT IS NOT NECESSARY TO REVISE ALL |
| SHEETS. |
| |
| 6. THIS SUBMITTAL WILL BE ISSUED WITH PROVISO: |
| |
| THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS. |
| 2010 FBC-B 2204.1 WELDING |
| 2010 FBC-B 2204.4.2 BOLTING. |
| |
| |