2017-01-30 06:12:43 | 1) INDICATE THE SIZE AND THE CORRESPONDING EHD OF THE |
| CSST BEING INSTALLED. WPB AMENDMENTS TO FBC |
| SEC.107.2.1. |
| 2) SHOW THE LOCATION OF THE MEDIUM PRESSURE GAS |
| REGULATOR. A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS |
| SEC.409.4. |
| 3) INDICATE ON THE PLAN IF THE EXISTING TANK TYPE WATER |
| HEATER WAS GAS OR ELECTRIC. IF IT WAS ELECTRIC, THEN A |
| SEPARATE ELECTRIC PERMIT WILL BE REQUIRED. |
| 4) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER 2014 FBC-RES. |
| SEC.G2426. |
| 5) A PLAN HAS BEEN SUBMITTED SHOWING AND EN ELECTRIC |
| OUTLET AND SOME ADDITIONAL WRITING THAT IS ILLEGIBLE. |
| IS THIS ELECTRIC OUTLET NEW OR EXISTING? CLARIFY THE |
| ADDITIONAL WRITING ON THE PLAN THAT CANNOT BE READ. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A |
| COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. IN ADDITION, SUBMIT TWO COPIES OF THE PAGE FROM |
| THE MANUFACTURER'S INSTALLATION MANUAL THAT SHOWS THE |
| REQUIRED CLEARANCES FROM OPERABLE WINDOWS AND DOORS. |
| 8) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE |
| DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR |
| OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3. |
| 9) SOME OF THE INFORMATION ON THE PLAN IS CUT OFF THE |
| PAGE. SUBMIT A PLAN WITH ALL NOTES.WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| |