2017-02-13 14:41:53 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. |
| |
| 2) SPECIFY THE APPLICABLE CATEGORY OF THE SUNROOM ON |
| THE PLANS. FBC-R301.2.1.1.2.2 - FOR THE PURPOSE OF |
| APPLYING THE CRITERIA OF THE AAMA/NPEA/NSA 2100, |
| SUNROOMS SHALL BE CATEGORIZED IN ONE OF THE FOLLOWING |
| CATEGORIES BY THE PERMIT APPLICANT, DESIGN PROFESSIONAL |
| OR THE PROPERTY OWNER WHERE THE SUNROOM IS BEING |
| CONSTRUCTED. |
| |
| CATEGORY I: A THERMALLY ISOLATED SUNROOM WITH WALLS |
| THAT ARE EITHER OPEN OR ENCLOSED WITH INSECT SCREENING |
| OR 0.5 MM (20 MIL) MAXIMUM THICKNESS PLASTIC FILM. THE |
| SPACE IS DEFINED AS A NONHABITABLE, NONCONDITIONED |
| SUNROOM. |
| |
| CATEGORY II: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED |
| WALLS. THE OPENINGS ARE PERMITTED TO BE ENCLOSED WITH |
| TRANSLUCENT OR TRANSPARENT PLASTIC OR GLASS. THE SPACE |
| IS DEFINED AS A NONHABITABLE, NONCONDITIONED SUNROOM. |
| |
| CATEGORY III: A THERMALLY ISOLATED SUNROOM WITH |
| ENCLOSED WALLS. THE OPENINGS ARE PERMITTED TO BE |
| ENCLOSED WITH TRANSLUCENT OR TRANSPARENT PLASTIC OR |
| GLASS. THE SUNROOM FENESTRATION COMPLIES WITH |
| ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION RESISTANCE |
| AND WATER PENETRATION RESISTANCE. THE SPACE IS DEFINED |
| AS A NONHABITABLE, NONCONDITIONED SUNROOM. |
| |
| CATEGORY IV: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED |
| WALLS. THE SUNROOM IS DESIGNED TO BE HEATED AND/OR |
| COOLED BY A SEPARATE TEMPERATURE CONTROL OR SYSTEM AND |
| IS THERMALLY ISOLATED FROM THE PRIMARY STRUCTURE. THE |
| SUNROOM FENESTRATION COMPLIES WITH ADDITIONAL |
| REQUIREMENTS FOR AIR INFILTRATION RESISTANCE, WATER |
| PENETRATION RESISTANCE, AND THERMAL PERFORMANCE. THE |
| SPACE IS DEFINED AS A NONHABITABLE AND CONDITIONED |
| SUNROOM. |
| |
| CATEGORY V: A SUNROOM WITH ENCLOSED WALLS. THE SUNROOM |
| IS DESIGNED TO BE HEATED AND/OR COOLED AND IS OPEN TO |
| THE MAIN STRUCTURE. THE SUNROOM FENESTRATION COMPLIES |
| WITH ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION |
| RESISTANCE, WATER PENETRATION RESISTANCE, AND THERMAL |
| PERFORMANCE. THE SPACE IS DEFINED AS A HABITABLE AND |
| CONDITIONED SUNROOM. |
| |
| |