2017-02-13 14:41:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD.
  
 2) SPECIFY THE APPLICABLE CATEGORY OF THE SUNROOM ON
 THE PLANS. FBC-R301.2.1.1.2.2 - FOR THE PURPOSE OF
 APPLYING THE CRITERIA OF THE AAMA/NPEA/NSA 2100,
 SUNROOMS SHALL BE CATEGORIZED IN ONE OF THE FOLLOWING
 CATEGORIES BY THE PERMIT APPLICANT, DESIGN PROFESSIONAL
 OR THE PROPERTY OWNER WHERE THE SUNROOM IS BEING
 CONSTRUCTED.
  
 CATEGORY I: A THERMALLY ISOLATED SUNROOM WITH WALLS
 THAT ARE EITHER OPEN OR ENCLOSED WITH INSECT SCREENING
 OR 0.5 MM (20 MIL) MAXIMUM THICKNESS PLASTIC FILM. THE
 SPACE IS DEFINED AS A NONHABITABLE, NONCONDITIONED
 SUNROOM.
  
 CATEGORY II: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED
 WALLS. THE OPENINGS ARE PERMITTED TO BE ENCLOSED WITH
 TRANSLUCENT OR TRANSPARENT PLASTIC OR GLASS. THE SPACE
 IS DEFINED AS A NONHABITABLE, NONCONDITIONED SUNROOM.
  
 CATEGORY III: A THERMALLY ISOLATED SUNROOM WITH
 ENCLOSED WALLS. THE OPENINGS ARE PERMITTED TO BE
 ENCLOSED WITH TRANSLUCENT OR TRANSPARENT PLASTIC OR
 GLASS. THE SUNROOM FENESTRATION COMPLIES WITH
 ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION RESISTANCE
 AND WATER PENETRATION RESISTANCE. THE SPACE IS DEFINED
 AS A NONHABITABLE, NONCONDITIONED SUNROOM.
  
 CATEGORY IV: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED
 WALLS. THE SUNROOM IS DESIGNED TO BE HEATED AND/OR
 COOLED BY A SEPARATE TEMPERATURE CONTROL OR SYSTEM AND
 IS THERMALLY ISOLATED FROM THE PRIMARY STRUCTURE. THE
 SUNROOM FENESTRATION COMPLIES WITH ADDITIONAL
 REQUIREMENTS FOR AIR INFILTRATION RESISTANCE, WATER
 PENETRATION RESISTANCE, AND THERMAL PERFORMANCE. THE
 SPACE IS DEFINED AS A NONHABITABLE AND CONDITIONED
 SUNROOM.
  
 CATEGORY V: A SUNROOM WITH ENCLOSED WALLS. THE SUNROOM
 IS DESIGNED TO BE HEATED AND/OR COOLED AND IS OPEN TO
 THE MAIN STRUCTURE. THE SUNROOM FENESTRATION COMPLIES
 WITH ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION
 RESISTANCE, WATER PENETRATION RESISTANCE, AND THERMAL
 PERFORMANCE. THE SPACE IS DEFINED AS A HABITABLE AND
 CONDITIONED SUNROOM.
  
  