2017-01-27 11:08:08 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING |
| BUILDING CODE |
| |
| THIS IS A REVIEW FOR RE-ISSUANCE OF EXPIRED PERMIT |
| 05110768. THE PROJECT WAS COMPLETED BUT ALL REQUIRED |
| INSPECTIONS WERE NOT APPROVED. SEE R REVIEW FOR ROOF |
| COVERING REQUIREMENTS AND ELECTRIC REVIEW FOR |
| ELECTRICAL REQUIREMNTS. THERE IS NO RECORD OF A |
| REQUIRED INSULATION INSPECTION. YOU MUST SATISFY THE |
| INSPECTOR BY CERTIFICATION TEST OR EXPOSING THE WORK |
| SUFFICIENTLY TO VERIFY THE INSTALLATION. REF. FBC 110. |
| PLEASE NOTE THE PLAN SHOW AN EXTERIOR HARDIPLANK |
| SIDING, HOWEVER UNDER PERMIT 07070773, A CHANGE WAS |
| MADE TO STUCCO AND THAT PERMIT RECEIVED THE REQUIRED |
| INSPECTIONS. THIS IS NOTED ON THE PLAN FOR RECORD |
| PURPOSES. PLEASE NOTE THE OWNER INDICATES THE STORM |
| PANELS ON FILE FROM THE ORIGINAL PERMIT DOCUMENTS ARE |
| NOT PROVIDED ON SITE. ACCORDINGLY, A LICENSED |
| CONTRACTOR MUST BE ENGAGED BY THE OWNER AND A SEPARATE |
| PERMIT MUST BE OBTAINED TO INSTALL NEW CODE COMPLIANT |
| SHUTTERS FOR THE NEW WINDOW OPENINGS ON THE EXTERIOR |
| WALLS SHOWN ON THE RECORD SET OF PLANS 05110768. REF |
| FBC R301.2.1.2 PROTECTION OF OPENINGS AND FS 489.103. A |
| FINAL INSPECTION WAS NEVER SCHEDULED AND IS REQUIRED |
| HOWEVER, IT MAY NOT BE SCHEDULED UNTIL SUCH TIME AS THE |
| HURRICANE PANEL, ELECTRICAL AND ROOFING PERRMITS ARE |
| COMPLETED AND HAVE RECEIVED FINAL APPROVED INSPECTIONS. |
| . |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |
| (561) 805-6710 |
| [email protected] |
| |