2017-01-19 13:01:13RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- THERE IS AN ENGINEER OF RECORD WHO DESIGNED THE
 MECHANICAL PLANS. PLANS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD SHOWN ON THE BOTTOM RIGHT OF
 PLANS. CHAPTER 471 FLORIDA STATUTE.
  
 2- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW
 EQUIPMENT IS 16 SEER. ORIGINAL PLANS AND ENERGY
 CALCULATIONS WERE APPROVED WITH 19.50 SEER. NEED TO
 PROVIDE EQUIPMENT WITH 19.50 SEER EFFICIENCY OR
 ENGINEER OF RECORD WHO PERFORMED THE ENERGY
 CALCULATIONS NEED TO REVISE THE ENERGY CALCULATIONS
 ACCORDINGLY. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 3- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  