Plan Review Notes For Permit 17010356 |
Permit Number |
17010356 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-19 13:01:13 | RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- THERE IS AN ENGINEER OF RECORD WHO DESIGNED THE | | MECHANICAL PLANS. PLANS NEED TO BE SIGNED AND SEALED BY | | THE ENGINEER OF RECORD SHOWN ON THE BOTTOM RIGHT OF | | PLANS. CHAPTER 471 FLORIDA STATUTE. | | | | 2- EQUIPMENT MANUFACTURER WAS CHANGED. THE SEER FOR NEW | | EQUIPMENT IS 16 SEER. ORIGINAL PLANS AND ENERGY | | CALCULATIONS WERE APPROVED WITH 19.50 SEER. NEED TO | | PROVIDE EQUIPMENT WITH 19.50 SEER EFFICIENCY OR | | ENGINEER OF RECORD WHO PERFORMED THE ENERGY | | CALCULATIONS NEED TO REVISE THE ENERGY CALCULATIONS | | ACCORDINGLY. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH | | EDITION (2014). | | | | 3- LIVING ROOM NEEDS TO COMPLY WITH THE BALANCED RETURN | | AIR SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|