Plan Review Notes
Plan Review Notes For Permit 17010300
Permit Number 17010300
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-01-20 11:03:47PERMIT # 17010300
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PASSED PROVISO:
  
 1) ONE OR MORE VISUAL DEVICE (STROBE) IS NEEDED IN THE
 WALK-IN COOLER/FREEZER.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
  
 SANDRA THOMAS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4728
  