Plan Review Notes For Permit 17010300 |
Permit Number |
17010300 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-20 11:03:47 | PERMIT # 17010300 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PASSED PROVISO: | | | | 1) ONE OR MORE VISUAL DEVICE (STROBE) IS NEEDED IN THE | | WALK-IN COOLER/FREEZER. | | | | 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | SANDRA THOMAS | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4728 | | |
|