2017-01-12 12:27:032001 SOUTH DIXIE HIGHWAY
 TRACKING #17010266
 PERMIT #16041215
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE RESCUE HAS NO OBJECTIONS TO THE PRODUCT (DC315
 INTUMESCENT PAINT) UTILIZED TO PROTECT THE EXISTING
 SPRAY POLYURETHANE FOAM (SPF). NOTE THE MANUFACTURER'S
 APPLICATION REQUIREMENTS ARE VERY SPECIFIC AND REQUIRE
 DOCUMENTATION. REFERENCE PAINTTOPROTECT.COM DC315. THE
 PLAN REVIEW HAS BEEN APPROVED FOR THIS PRODUCT;
 HOWEVER, IN ORDER TO PASS INSPECTION THE MANUFACTURER'S
 REQUIREMENTS FOR APPLICATION DOCUMENTATION MUST BE
 PROVIDED.
  
 PRODUCT SPECIFICATIONS INDICATE:
  
 APPLICATOR SHALL PERFORM CONTINUOUS WET FILM THICKNESS
 CHECKS, MINIMUM 1 PER 100 SQUARE FEET. MEDALLIONS SHALL
 BE INSTALLED AT MINIMUM OF 1 PER 400 SQUARE FEET AND
 SHALL BE MAINTAINED WITH CONTRACT DOCUMENTS FOR
 VERIFICATION OF DRY FILM THICKNESS. APPLICATOR SHALL
 COMPLETE A JOB WORK REPORT THAT INCLUDES AMBIENT
 CONDITIONS, APPLICATION THICKNESS AND RESULTS OF
 ADHESION TESTING. UPON COMPLETION, A JOB SITE LABEL
 SHALL BE AFFIXED IN AN AREA SUCH AS THE ELECTRICAL
 PANEL AND SHALL INCLUDE APPLICATOR NAME AND CONTACT
 INFORMATION, COMPANY INFORMATION, PRODUCTS USED,
 MEASURED APPLICATION THICKNESS. JOB WORK REPORTS MUST
 BE SUBMITTED TO IFRM MANUFACTURER WITHIN 7 DAYS OF
 COMPLETION OF PROJECT.
  
 REQUIRED SURFACES SHALL BE PRIMED WITH A COMPATIBLE
 PRIMER APPROVED BY THE THIN-FILM FIRE RESISTIVE
 MATERIALMANUFACTURER.
  
 THE THIN-FILM FIRE RESISTIVE MATERIAL SHALL BE APPLIED
 AT THE REQUIRED DRY FILM THICKNESS PER THE APPROPRIATE
 SPF TEST REPORT AND MANUFACTURERS WRITTEN APPLICATION
 INSTRUCTIONS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  