2017-01-12 09:25:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE W-44 ROOFING SYSTEM NUMBER THAT WAS SELECTED ON | | PAGE 11 OF THE PRODUCT APPROVAL ( FL5293-R23) HAS A | | MAXIMUM DESIGN PRESSURE OF -52.5 PSF. ROOF ZONES 2 AND | | 3 ARE REQUIRED TO HAVE ENHANCED FASTENING CALCULATED BY | | A QUALIFIED DESIGN PROFESSIONAL. SUBMIT TWO SETS OF | | SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS. SEE | | NOTE 9 ON SHEET 3 OF THE EVALUATION REPORT. NOTE: THE | | CALCULATIONS THAT WERE SUBMITTED WITH THE ORIGINAL | | APPLICATION IS SPECIFIC TO NOA NO. 15-0729.18 (PAGES | | 14, 15 OF 27). |
|