Plan Review Notes For Permit 17010258 |
Permit Number |
17010258 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-02-16 17:00:52 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | 1. SEE GENERAL LIMITATION #7, THE ASSEMBLY SELECTED IS | | TO MEET THE DESIGN PRESSURES FOR ZONE 1. ENGINEERING | | SPECIFIES FIELD AREA AS -73 PSF, ASSEMBLY IS LIMITED TO | | -52.5 PSF. | | | | 2. FBC 5TH EDITION RESIDENTIAL FIGURE 301.2(7), ZONE 3 | | TO EQUAL 4' IN ALL CASES. PLEASE REVISE NOTE 1 WHICH | | SPEFICIES "NOT LESS THAN 3'-0"". | | | | 3. ZONE 2 SPECIFIES 5.8"; SEE RAS 117 10.4.5, ALL | | FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER. | | | | 3. ZONE 3 SPECIFIES 4.3" SPACING; SEE RAS 117 10.4.5, | | ALL FRACTIONS TO BE ROUNDED DOWN TO THE NEXT WHOLE | | NUMBER. | | | | 4. ALL PRODUCT APPROVALS IN THE SUBMITTAL WERE MARKED | | "VOID" BY THE APPLICANT. PROVIDE TWO SETS OF EACH | | PRODUCT APPROVAL (FLAT DECK, SHINGLES). | | | | | | |
|