2017-01-27 18:54:15 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SUBMIT TWO SETS OF A RECENT SURVEY. FBC 107.2.1 |
| |
| 2) A SEPARATE PERMIT, APPLICATION AND REVIEW IS |
| REQUIRED FOR A FENCE PERMIT. |
| |
| 3) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AS |
| REQUIRED BY FBC ENERGY CONSERVATION SECTION R101.5.1.1. |
| |
| 4) SHOW COMPLIANCE WITH FBC-R 806.2 MINIMUM VENT AREA. |
| THE MINIMUM NET FREE VENTILATING AREA SHALL BE 1/150 OF |
| THE AREA OF THE VENTED SPACE. |
| |
| 5) SHOW COMPLIANCE WITH FBC-R408.2 OPENINGS FOR |
| UNDER-FLOOR VENTILATION. THE MINIMUM NET AREA OF |
| VENTILATION OPENINGS SHALL NOT BE LESS THAN 1 SQUARE |
| FOOT FOR EACH 150 SQUARE FEET OF UNDER-FLOOR AREA. ONE |
| VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF |
| EACH CORNER OF THE BUILDING. |
| |
| 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| AND MAXIMUM DESIGN PRESSURES FOR THE STRUCTURAL |
| MULLIONS. |
| |
| |
| |
| |
| |
| |
| |