Plan Review Notes
Plan Review Notes For Permit 17010186
Permit Number 17010186
Review Stop B
Sequence Number 1
Notes
Date Text
2017-01-27 18:54:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF A RECENT SURVEY. FBC 107.2.1
  
 2) A SEPARATE PERMIT, APPLICATION AND REVIEW IS
 REQUIRED FOR A FENCE PERMIT.
  
 3) SUBMIT TWO SETS OF ENERGY CODE COMPLIANCE FORMS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTION R101.5.1.1.
  
 4) SHOW COMPLIANCE WITH FBC-R 806.2 MINIMUM VENT AREA.
 THE MINIMUM NET FREE VENTILATING AREA SHALL BE 1/150 OF
 THE AREA OF THE VENTED SPACE.
  
 5) SHOW COMPLIANCE WITH FBC-R408.2 OPENINGS FOR
 UNDER-FLOOR VENTILATION. THE MINIMUM NET AREA OF
 VENTILATION OPENINGS SHALL NOT BE LESS THAN 1 SQUARE
 FOOT FOR EACH 150 SQUARE FEET OF UNDER-FLOOR AREA. ONE
 VENTILATION OPENING SHALL BE WITHIN 3 FEET (915 MM) OF
 EACH CORNER OF THE BUILDING.
  
 6) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE STRUCTURAL
 MULLIONS.
  
  
  
  
  
  
  