Plan Review Notes
Plan Review Notes For Permit 17010157
Permit Number 17010157
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2017-03-14 09:31:46NFPA 14-6.4, 2012 FIRE DEPARTMENT CONNECTIONS. SHALL BE
 LOCATED NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST
 FIRE HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
 6.4.5.4.1 THE LOCATION OF THE FIRE DEPARTMENT
 CONNECTION SHALL BE PERMITTED TO EXCEED 100 FT (30.5 M)
 SUBJECT TO THE APPROVAL OF THE AUTHORITY HAVING
 JURISDICTION.
  
 FIRE PUMP INTALLATION SHALL COME IN COMPLIANCE WITH
 NFPA 20.
  
 NFPA 72-5.15 SUPERVISORY SIGNAL-INITIATING DEVICES:
 5.15.1 CONTROL VALVE SUPERVISORY SIGNAL-INITIATING
 DEVICE. 5.15.1.1 TWO SEPARATE AND DISTINCT SIGNALS
 SHALL BE INITIATED: ONE INDICATING MOVEMENT OF THE
 VALVE FROM ITS NORMAL POSITION (OFF-NORMAL) AND THE
 OTHER INDICATING RESTORATION OF THE VALVE TO ITS NORMAL
 POSITION.
  
 5.15.1.2 THE OFF-NORMAL SIGNAL SHALL BE INITIATED
 DURING THE FIRST TWO REVOLUTIONS OF THE HAND WHEEL OR
 DURING ONE-FIFTH OF THE TRAVEL DISTANCE OF THE VALVE
 CONTROL APPARATUS FROM ITS NORMAL POSITION. 5.15.1.3
 THE OFF-NORMAL SIGNAL SHALL NOT BE RESTORED AT ANY
 VALVE POSITION EXCEPT NORMAL. 5.15.1.4 AN INITIATING
 DEVICE FOR SUPERVISING THE POSITION OF A CONTROL VALVE
 SHALL NOT INTERFERE WITH THE OPERATION OF THE VALVE,
 OBSTRUCT THE VIEW OF ITS INDICATOR, OR PREVENT ACCESS
 FOR VALVE MAINTENANCE.
  
 FRANK STALLWORTH, FIRE INSPECTOR I
 WEST PALM BEACH FIRE PREVENTION BUREAU
 500 N. DIXIE HWY
 WEST PALM BEACH, FLORIDA 33401
 OFFFICE: 561-840-4780
 FAX: 561-840-4774
 [email protected]
  