2017-01-10 17:21:57 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| |
| 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS |
| |
| (1) PROVIDE INFORMATION ON PLANS. ENGINEER OR ARCHITECT |
| STAMP AND SIGNATURE. (AS PER 107.1 GENERAL) SEE BELOW |
| |
| 107.1 GENERAL. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT, INTERIOR |
| DESIGNER, LANDSCAPE ARCHITECT, OR ENGINEER LEGALLY |
| REGISTERED UNDER THE LAWS OF THIS STATE REGULATING THE |
| PRACTICE OF ARCHITECTURE OR INTERIOR DESIGN AS |
| PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART I, |
| OR LANDSCAPE ARCHITECTURE AS PROVIDED FOR IN |
| CHAPTER 481, FLORIDA STATUTES, PART II, OR ENGINEERING |
| AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| |
| (2) PROVIDE EQUIPMENT SCHEDULE ON PLANS. ( BRAND, AHU |
| MODEL #, CONDENSER MODEL #, TOTAL BTUH, KW HEATER, |
| SEER) |
| (3) PROVIDE BALANCE RETURN FROM ALL HABITABLE ROOMS (AS |
| PER M1602.4 BALANCED RETURN AIR) |
| (4) PROVIDE EXHAUST IN ALL BATHROOMS. (MINIMUN 50 CFM) |
| (5) KITCHEN EXHAUST ????? |
| (6) PROVIDE CONDENSER TIE DOWN DETAIL. (AS PER |
| MANUFACTURER, IF APPLICABLE) |
| |