Plan Review Notes
Plan Review Notes For Permit 17010155
Permit Number 17010155
Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-18 15:10:45MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] ELECTRICAL REVIEW UNDER 16120490
  
 2] CONDENSER UNIT REQUIRESA SERVICE GFCI RECEPTACLE
 OUTLET WITHIN 25' OF EQUIPMENT PER FBC-R SEC E3901.11
 (PROVISO COMMENT)
  
 3] PROVIDE A DISCONNECT WITHIN SIGHT OF THE CONDENSER
 UNIT PER FBC-R SEC E4101.5 (PROVISO COMMENT)