2017-01-10 09:41:11 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| REVISION DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SHEETS A-7 AND A-8 WILL NEED TO BE REVISED TO SHOW |
| THE NEW 17 FT WIDE WINDOW. FBC 107.2.1 |
| |
| 2) THE REVISED PLANS SHOW A 17 FT WIDE WINDOW THAT IS |
| LOCATED BEHIND THE RANGE IN THE KITCHEN. THIS IS |
| TYPICALLY NOT ALLOWED. M1901.1 CLEARANCES. FREESTANDING |
| OR BUILT-IN RANGES SHALL HAVE A VERTICAL CLEARANCE |
| ABOVE THE COOKING TOP OF NOT LESS THAN 30 INCHES (762 |
| MM) TO UNPROTECTED COMBUSTIBLE MATERIAL. |
| |
| 3) THE PRODUCT APPROVAL, NOA NO. 15-0528.26, THAT WAS |
| SUBMITTED FOR THE FIXED GLASS WINDOWS HAS A MAXIMUM |
| LONG SIDE OF 144" OR 12 FEET. SUBMIT A PRODUCT APPROVAL |
| FOR A WINDOW THAT HAS A 17 FT OR MORE LONG SIDE. |
| ALTERNATELY, BREAK UP THE WINDOW WITH STRUCTURAL |
| MULLIONS. DCA RULE 9N-3 |
| |
| 4) SPECIFY THE BEAM/LINTEL THAT WILL BE USED TO SPAN |
| THE 17 FT WIDE OPENING FOR THE PROPOSED WINDOW AND |
| PROVIDE STRUCTURAL DETAILS OF THE BEAM AND COLUMNS FOR |
| CLARIFICATION. FBC 107.2.1.3 |
| |
| 5) THE REVISION TO THE BEAM SCHEDULE IS MARKED #5 ON |
| SHEET S-2 AND #3 ON SHEET S-3. PLEASE CORRECT. FBC |
| 107.2.1 |
| |
| 6) THE PLANS INDICATE A REVISION TO THE ROOF THAT |
| ELIMINATES THE ROOF DRAINS AND SLOPES THE ROOF 1/8 INCH |
| PER FOOT TO THE ROOF EDGES. THE ROOF COVERING MATERIAL |
| IS SPECIFIED AS MODIFIED BITUMEN AND THE PRODUCT |
| APPROVAL, FL# 16429-R5, THAT WAS SUBMITTED IS FOR |
| MODIFIED BITUMEN. CODE REQUIRES A MINIMUM SLOPE OF 1/4 |
| INCH PER FOOT. FBC-R905.11.1 SLOPE. MODIFIED BITUMEN |
| MEMBRANE ROOFS SHALL HAVE A DESIGN SLOPE OF A MINIMUM |
| OF ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) FOR DRAINAGE. |
| |
| 7) THIS STRUCTURE DOES NOT HAVE ANY OVERHANGS AND THERE |
| ARE NO GUTTERS WITH DOWNSPOUTS SHOWN OR SPECIFIED ON |
| THE DRAWINGS. THE PLANS DO NOT SHOW COMPLIANCE WITH |
| FBC- R318.5 PROTECTION AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES, IRRIGATION/SPRINKLER SYSTEM RISERS |
| FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| |
| |
| |