Plan Review Notes For Permit 17010073 |
Permit Number |
17010073 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-25 18:31:41 | 3RD REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] MAIN DISCONNECT SHALL BE LOCATED OUTSIDE AT THE | | NEAREST POINT OF ENTRANCE TO THE SERVICE CONDUCTORS. | | NEC 230.70(A)(1) | | - UNFUSED SERVICE WIRES CANNOT PASS BY THE INSIDE OF | | THE BUILDING. |
|