Review Stop E
Sequence Number 1
Notes
Date Text
2017-01-05 18:47:541ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] IN ADDITION TO THE RISER DIAGRAM PROVIDE LOAD
 CALCULATIONS & PANEL SCHEDULE. FBC 107.3.5.3
  
 2] CLARIFY IF MAIN DISCONNECT IS LOCATED INSIDE OR
 OUTSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS PER NEC 230.70(A)(1).
  
 3] ADD AN INTERSYSTEM BONDING TERMINAL IN ACCORDANCE
 WITH NEC 250.94.