Plan Review Notes For Permit 17010073 |
Permit Number |
17010073 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-05 18:47:54 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] IN ADDITION TO THE RISER DIAGRAM PROVIDE LOAD | | CALCULATIONS & PANEL SCHEDULE. FBC 107.3.5.3 | | | | 2] CLARIFY IF MAIN DISCONNECT IS LOCATED INSIDE OR | | OUTSIDE NEAREST THE POINT OF ENTRANCE OF THE SERVICE | | CONDUCTORS PER NEC 230.70(A)(1). | | | | 3] ADD AN INTERSYSTEM BONDING TERMINAL IN ACCORDANCE | | WITH NEC 250.94. |
|