Plan Review Notes
Plan Review Notes For Permit 17010015
Permit Number 17010015
Review Stop B
Sequence Number 2
Notes
Date Text
2017-05-08 15:54:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE ENERGY SUBMITTAL. PROVIDE R VALUE OF CEILING
 INSULATION.
 3. IDENTIFY THE ICYNENE SYSTEM THAT WILL BE USED PER
 ICC-EVALUATION SERVICE REPORT ESR-1826 TO MEET THE
 REQUIREMENTS OF THE ENERGY SUBMITTAL INSULATION VALUES.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
  