Plan Review Notes
Plan Review Notes For Permit 17010014
Permit Number 17010014
Review Stop M
Sequence Number 1
Notes
Date Text
2017-01-25 14:05:341ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010014
 1/25/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS PER
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) PROVIDE DOCUMENTATION OF ENERGY CONSERVSATION
 COMPLIANCE IN ACCORDANCE WITH SECTIONS C101.3 AND
 C401.2.
  
 3) THE AC CLOSET DOOR MUST BE NON-COMBUSTIBLE OR
 PLENUM-RATED PER SECTION C403.2.7.2.
  
 4) THE GRAVITY RELIEF ROOF CAP MUST BE ANCHORED TO
 RESIST THE WIND LOAD AND PRESSURES- SECTION 301.15
 FBC-14 MECHANICAL. PROVIDE ENGINEERED DETAILS.
  
 5) THE MIAMI-DADENOA #12-0628.05 FOR THE LOUVER IS
 EXPIRED. PLEASE PROVIDE A CURRENT NOA # ON THE PLAN AND
 SUBMIT TWO COPIES OF THE DOCUMENT.
  
 6) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROPOSED PROJECT.
  
 7) TWO SETS OF PLANS ARE REQUIRED FOR REVIEW AND
 PERMITTING- SECTION 107.1 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  