2017-01-23 10:59:05THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL,
 WITH THE FOLLOWING COMMENTS:
  
  
 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM
 RESIDENTIAL TO BUSINESS AND COMPLY WITH THE APPLICABLE
 CODES OF THE FLORIDA FIRE PREVENTION CODE.
  
  
 2 ) THE EXIT RAMP IS INDICATED AS PASSING BY THREE
 SINGLE HUNG WINDOWS. THE RAMP IS A EXIT ACCESS AND ITS
 USE SHALL BE PROTECTED. THE WINDOWS ARE A POTENTIAL
 EXPOSURE HAZARD TO THOSE USING THE RAMPS AND SHALL BE
 PROTECTED PER NFPA 101, CHAPTER 38 NEW BUSINESS
 OCCUPANCIES AND CHAPTER 7, MEANS OF EGRESS.
  
 38.2.2 MEANS OF EGRESS COMPONENTS.
 38.2.2.1 COMPONENTS PERMITTED. MEANS OF EGRESS
 COMPONENTS SHALL BE LIMITED TO THE TYPES DESCRIBED IN
 38.2.2.2 THROUGH 38.2.2.12.
  
 38.2.2.6 RAMPS. RAMPS COMPLYING WITH 7.2.5 SHALL BE
 PERMITTED
  
 7.2.5 RAMPS.
 7.2.5.1 GENERAL. EVERY RAMP USED AS A COMPONENT IN A
 MEANS OF EGRESS SHALL CONFORM TO THE GENERAL
 REQUIREMENTS OF SECTION 7.1 AND TO THE SPECIAL
 REQUIREMENTS OF 7.2.5.
  
 7.2.5.5 ENCLOSURE AND PROTECTION OF RAMPS. RAMPS IS A
 REQUIRED MEANS OF EGRESS SHALL BE ENCLOSED OR PROTECTED
 AS A STAIR IN ACCORDANCE WITH 7.2.2.5 AND 7.2.2.6.
  
 7.2.2.5.2* EXPOSURES.
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN
 AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE
 EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF
 LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS
 WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED
 WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS
 REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING
 PROTECTIVES.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY CONSTRUCTION WITH THE FIRE
 RESISTANCE RATING REQUIRED FOR ENCLOSED STAIRS WITH
 FIXED OR SELF-CLOSING OPENING PROTECTIVES, EXCEPT AS
 FOLLOWS:
 (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS
 BALCONY THAT HAS TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS
 SHALL BE PERMITTED TO BE UNPROTECTED.
 (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT
 STORIES, INCLUDING THE STORY WHERE THE EXIT DISCHARGES,
 SHALL BE PERMITTED TO BE UNPROTECTED WHERE THERE IS A
 REMOTELY LOCATED SECOND EXIT.
 (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS
 SERVING THREE OR FEWER ADJACENT STORIES, INCLUDING THE
 STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED TO
 BE UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND
 EXIT.
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050 MM) FROM THE STAIRS SHALL NOT BE
 REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS HAVE A MINIMUM
 ?-HOUR FIRE PROTECTION RATING.
 (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7 SHALL
 BE PERMITTED TO BE UNPROTECTED. 7.2.2.6.3.2 WALL
 CONSTRUCTION REQUIRED BY 7.2.2.6.3.1 SHALL EXTEND AS
 FOLLOWS:
 (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A
 POINT 10 FT (3050 MM) ABOVE THE TOPMOST LANDING OF THE
 STAIRS OR TO THE ROOFLINE, WHICHEVER IS LOWER
 (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM)
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL