2017-01-23 10:59:05 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, |
| WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM |
| RESIDENTIAL TO BUSINESS AND COMPLY WITH THE APPLICABLE |
| CODES OF THE FLORIDA FIRE PREVENTION CODE. |
| |
| |
| 2 ) THE EXIT RAMP IS INDICATED AS PASSING BY THREE |
| SINGLE HUNG WINDOWS. THE RAMP IS A EXIT ACCESS AND ITS |
| USE SHALL BE PROTECTED. THE WINDOWS ARE A POTENTIAL |
| EXPOSURE HAZARD TO THOSE USING THE RAMPS AND SHALL BE |
| PROTECTED PER NFPA 101, CHAPTER 38 NEW BUSINESS |
| OCCUPANCIES AND CHAPTER 7, MEANS OF EGRESS. |
| |
| 38.2.2 MEANS OF EGRESS COMPONENTS. |
| 38.2.2.1 COMPONENTS PERMITTED. MEANS OF EGRESS |
| COMPONENTS SHALL BE LIMITED TO THE TYPES DESCRIBED IN |
| 38.2.2.2 THROUGH 38.2.2.12. |
| |
| 38.2.2.6 RAMPS. RAMPS COMPLYING WITH 7.2.5 SHALL BE |
| PERMITTED |
| |
| 7.2.5 RAMPS. |
| 7.2.5.1 GENERAL. EVERY RAMP USED AS A COMPONENT IN A |
| MEANS OF EGRESS SHALL CONFORM TO THE GENERAL |
| REQUIREMENTS OF SECTION 7.1 AND TO THE SPECIAL |
| REQUIREMENTS OF 7.2.5. |
| |
| 7.2.5.5 ENCLOSURE AND PROTECTION OF RAMPS. RAMPS IS A |
| REQUIRED MEANS OF EGRESS SHALL BE ENCLOSED OR PROTECTED |
| AS A STAIR IN ACCORDANCE WITH 7.2.2.5 AND 7.2.2.6. |
| |
| 7.2.2.5.2* EXPOSURES. |
| 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY, OTHER THAN |
| AN EXISTING STAIRWAY, AND THE WALLS OR OPENINGS ARE |
| EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF |
| LESS THAN 180 DEGREES, THE BUILDING ENCLOSURE WALLS |
| WITHIN 10 FT (3050 MM) HORIZONTALLY OF THE NONRATED |
| WALL OR UNPROTECTED OPENING SHALL BE CONSTRUCTED AS |
| REQUIRED FOR STAIRWAY ENCLOSURES, INCLUDING OPENING |
| PROTECTIVES. |
| |
| 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| INTERIOR OF THE BUILDING BY CONSTRUCTION WITH THE FIRE |
| RESISTANCE RATING REQUIRED FOR ENCLOSED STAIRS WITH |
| FIXED OR SELF-CLOSING OPENING PROTECTIVES, EXCEPT AS |
| FOLLOWS: |
| (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS |
| BALCONY THAT HAS TWO REMOTE OUTSIDE STAIRWAYS OR RAMPS |
| SHALL BE PERMITTED TO BE UNPROTECTED. |
| (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT |
| STORIES, INCLUDING THE STORY WHERE THE EXIT DISCHARGES, |
| SHALL BE PERMITTED TO BE UNPROTECTED WHERE THERE IS A |
| REMOTELY LOCATED SECOND EXIT. |
| (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS |
| SERVING THREE OR FEWER ADJACENT STORIES, INCLUDING THE |
| STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED TO |
| BE UNPROTECTED WHERE THERE IS A REMOTELY LOCATED SECOND |
| EXIT. |
| (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| EXTENDING 10 FT (3050 MM) FROM THE STAIRS SHALL NOT BE |
| REQUIRED TO EXCEED 1 HOUR WHERE OPENINGS HAVE A MINIMUM |
| ?-HOUR FIRE PROTECTION RATING. |
| (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC |
| SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7 SHALL |
| BE PERMITTED TO BE UNPROTECTED. 7.2.2.6.3.2 WALL |
| CONSTRUCTION REQUIRED BY 7.2.2.6.3.1 SHALL EXTEND AS |
| FOLLOWS: |
| (1) VERTICALLY FROM THE FINISHED GROUND LEVEL TO A |
| POINT 10 FT (3050 MM) ABOVE THE TOPMOST LANDING OF THE |
| STAIRS OR TO THE ROOFLINE, WHICHEVER IS LOWER |
| (2) HORIZONTALLY FOR NOT LESS THAN 10 FT (3050 MM) |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |