Plan Review Notes
Plan Review Notes For Permit 16120959
Permit Number 16120959
Review Stop P
Sequence Number 1
Notes
Date Text
2016-12-31 08:00:541) INDICATE ON THE SITE PLAN IF THE IRRIGATION SYSTEM
 IS CONNECTED TO THE DOMESTIC WATER SERVICE LINE OR IF
 THERE IS GOING TO BE A SEPARATE METER & WATER SERVICE
 FOR THE IRRIGATION SYSTEM.IF A SEPARATE METER AND WATER
 SERVICE IS TO BE PROVIDED, THE LOCATION OF THE BACKFLOW
 DEVICE SHALL BE AS CLOSE TO THE METER AS POSSIBLE.
 CONTACT CITY OF WPB UTILITIES AT 561-822-2240 FOR
 DIRECTION ON LOCATION REQUIREMENTS FOR THE BACKFLOW
 DEVICE.
 2) SUBMIT TWO COPIES OF MANUF. SPECIFICATIONS FOR THE
 BACKFLOW DEVICE. THE DEVICE SHALL BE LEAD FREE PER CWPB
 CROSS-CONNECTION CONTROL MANUAL.
 3) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FROM A
 LICENSED PLUMBIG CONTRACTOR TO PROVIDE A CONNECTION AND
 INSTALL THE BACKFLOW PREVENTER ON THE SYSTEM. THE
 IRRIGATION CONTRACTOR SHALL CONNECT THE IRRIGATION
 SYSTEM TO THE OUTLET OF THE BACKFLOW PREVENTER. AN
 IRRIGATION LICENSE DOES NOT PERMIT THE IRRIGATION
 CONTRACTOR TO CONNECT TO THE POTABLE WATER SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  