Date |
Text |
2017-05-09 17:39:11 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) ROOF TILE SELF-ADHERED UNDERLAYMENT AS SPECIFIED ON |
| PLANS. |
| RESPONSE: REPEAT COMMENT. |
| |
| B) FLAT ROOF AS SHOWN ON PLANS FOR GARAGE AND ROOF DECK |
| ABOVE FRONT PORCH. AND CLEARLY IDENTIFY WHICH APPROVED |
| ASSEMBLY IS GOING TO BE USED. AND, PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| DOESN'T MEET THE CALCULATED DESIGN PRESSURES. NOTE: |
| VERIFY THAT SELECTED ASSEMBLY ALLOWS FOR RAS 117 |
| CALCULATIONS. |
| RESPONSE: REPEAT COMMENT. THERE ARE TWO DIFFERENT |
| PRODUCT APPROVALS SUBMITTED: FLORIDA PRODUCT APPROVAL |
| FL16709 AND NOA 13-1217.01. CLARIFY WHICH ONE IS GOING |
| TO BE USED IN THIS PROJECT. OR IF USING BOTH, THEN |
| CLEARLY SPECIFY WHERE EACH PRODUCT APPROVAL IS GOING TO |
| BE INSTALLED: GARAGE OR MAIN HOUSE ROOF DECK ABOVE |
| FRONT PORCH. NOTES: (1) IT'S NOT CLEAR WHY SEVERAL |
| ASSEMBLIES WHERE MARKED ON FLORIDA PRODUCT APPROVAL |
| FL16709-R3. CLEARLY IDENTIFY WHICH ONE IS GOING TO BE |
| USED. (2) DEPENDING ON ASSEMBLY SELECTED FROM NOA |
| 13-1217.01 SIGNED AND SEALED RAS 117 CALCULATIONS MAY |
| BE REQUIRED. |
| |
| C) RIDGE VENT FOR CONCRETE TILES AS SPECIFIED ON PLANS. |
| |
| 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT |
| SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| |