2017-05-09 17:39:111- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE SELF-ADHERED UNDERLAYMENT AS SPECIFIED ON
 PLANS.
 RESPONSE: REPEAT COMMENT.
  
 B) FLAT ROOF AS SHOWN ON PLANS FOR GARAGE AND ROOF DECK
 ABOVE FRONT PORCH. AND CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE USED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE CALCULATED DESIGN PRESSURES. NOTE:
 VERIFY THAT SELECTED ASSEMBLY ALLOWS FOR RAS 117
 CALCULATIONS.
 RESPONSE: REPEAT COMMENT. THERE ARE TWO DIFFERENT
 PRODUCT APPROVALS SUBMITTED: FLORIDA PRODUCT APPROVAL
 FL16709 AND NOA 13-1217.01. CLARIFY WHICH ONE IS GOING
 TO BE USED IN THIS PROJECT. OR IF USING BOTH, THEN
 CLEARLY SPECIFY WHERE EACH PRODUCT APPROVAL IS GOING TO
 BE INSTALLED: GARAGE OR MAIN HOUSE ROOF DECK ABOVE
 FRONT PORCH. NOTES: (1) IT'S NOT CLEAR WHY SEVERAL
 ASSEMBLIES WHERE MARKED ON FLORIDA PRODUCT APPROVAL
 FL16709-R3. CLEARLY IDENTIFY WHICH ONE IS GOING TO BE
 USED. (2) DEPENDING ON ASSEMBLY SELECTED FROM NOA
 13-1217.01 SIGNED AND SEALED RAS 117 CALCULATIONS MAY
 BE REQUIRED.
  
 C) RIDGE VENT FOR CONCRETE TILES AS SPECIFIED ON PLANS.
  
 2- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  