2017-01-20 11:48:15 | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) ARCHED ENTRY DOOR AS SHOWN ON PLANS. |
| |
| B) REAR EXTERIOR DOOR AS SHOWN ON PLANS. |
| |
| C) GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS. |
| |
| D) GARAGE OVERHEAD DOOR AS SHOWN ON PLANS. |
| |
| E) ARCHED AND RECTANGULAR SINGLE HUNG WINDOWS AS SHOWN |
| ON PLANS. |
| |
| F) ARCHED CASEMENT WINDOWS AS SHOWN ON PLANS. |
| |
| G) ROOF TILE AS SHOWN ON PLANS |
| |
| H) ROOF TILE RIDGE VENT AS SHOWN ON PLANS (SEE SHEET |
| A2.00). |
| |
| I) ROOF TILE ADHESIVE. |
| |
| J) ROOF TILE SELF-ADHERED UNDERLAYMENT AS SPECIFIED ON |
| SHEET S3.00 ON THE CUT SECTION DETAIL. |
| |
| K) FLAT ROOF AS SHOWN ON PLANS FOR GARAGE AND ROOF |
| ABOVE FRONT PORCH. AND CLEARLY IDENTIFY WHICH APPROVED |
| ASSEMBLY IS GOING TO BE USED. AND, PROVIDE SIGNED AND |
| SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY |
| DOESN'T MEET THE CALCULATED DESIGN PRESSURES. NOTE: |
| VERIFY THAT SELECTED ASSEMBLY ALLOWS FOR RAS 117 |
| CALCULATIONS. |
| |
| L) PRECAST LINTELS AS SHOWN ON PLANS/DETAILS. |
| |
| M) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| NUMBER NEXT TO EACH SPECIFIED CONNECTOR. |
| |
| N) HURRICANE SHUTTERS IF DOORS AND WINDOWS PRODUCT |
| APPROVALS SUBMITTED DON'T HAVE IMPACT GLAZING. AND |
| PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE. |
| |
| O) WINDOW MULLION AS SHOWN ON PLANS. AND, CLEARLY |
| SPECIFY SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED |
| DESIGN PRESSURES. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: |
| PRODUCT APPROVAL INFORMATION ON SHEET A1.00 NEEDS TO BE |
| REVISED. CONCRETE TILE NOA 11-0510.02 IS EXPIRED. NEED |
| CURRENT NOA. SINGLE HUNG WINDOWS FL15771 R0 NEEDS TO BE |
| UPDATED WITH THE CURRENT 2014 CODE. SWING DOOR FL8871 |
| R6 NEEDS TO BE UPDATED. NEED CURRENT R7 REVISION. NOTE: |
| IF USING THIS METHOD FOR PRODUCT APPROVAL REVIEW, THEN |
| LIST ALL THE PRODUCT APPROVALS. |
| |
| 4- SIZE OF WINDOWS SPECIFIED ON FLOOR PLANS AND |
| EXTERIOR ELEVATIONS IS NOT CLEAR. FOR EXAMPLE WHY ARE |
| THERE TWO DIFFERENT WAYS OF SPECIFYING SINGLE HUNG |
| WINDOWS. WHAT'S A SH#25 WINDOW? WHAT'S A SH 2050 |
| WINDOW?. PROVIDE COMPLETE AND CLEAR WINDOW SCHEDULE AND |
| SPECIFY ACTUAL SIZE OF WINDOWS TO VERIFY COMPLIANCE |
| WITH EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL, |
| 5TH EDITION (2014). NOTE: PROVIDE MANUFACTURER'S SPECS |
| SHOWING THE ACTUAL SIZE OF THE EGRESS WINDOWS. |
| |
| 5- PROVIDE SOIL TEST REPORT (2 COPIES). SEC. R401.4 |
| FBC-RESIDENTIAL. |
| |
| 6- PROVIDE DRAINAGE PLAN (2 COPIES) SHOWING COMPLIANCE |
| WITH SEC. R401.3 FBC-RESIDENTIAL. |
| |
| 7- SECOND FLOOR WINDOWS NEED TO COMPLY WITH THE WINDOW |
| FALL PROTECTION AS REQUIRED BY SEC. R312.2 |
| FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR THE WINDOWS ON THE SECOND FLOOR THAT |
| NEED TO COMPLY WITH THIS SECTION. |
| |
| 8- ATTIC VENTILATION INFORMATION ON SHEET A2.00: |
| A) ROOF RIDGE DIMENSION SHOWN ON THE EXTERIOR |
| ELEVATIONS IS LESS THAN THE REQUIRED 21 LINEAL FEET. IT |
| DOESN'T COMPLY WITH THE REQUIREMENTS FOR THE 1/300 |
| VENTILATION RATIO ALLOWED BY THE EXCEPTION OF SEC. |
| R806.2 FBC-RESIDENTIAL. REVISE INFORMATION ON SHEET |
| A2.00, SHEET A3.00 AND SHEET S3.00 AS REQUIRED. |
| |
| B) SPECIFY ON PLANS LOCATION OF SOFFIT VENTS. SEC. |
| R806.2 FBC-RESIDENTIAL. NOTE: TABLE R302.1(1) REQUIRES |
| ONE HOUR FIRE RATED ASSEMBLY ON THE UNDERSIDE OF THE |
| SOFFIT. THEREFORE VENTS ARE NOT ALLOWED ON THE EAST |
| SIDE. |
| |
| C) PROVIDE INFORMATION FOR THE ROOF VENTILATION AT THE |
| SEPARATE GARAGE STRUCTURE SHOWING COMPLIANCE WITH SEC. |
| R806.2 FBC-RESIDENTIAL. |
| |
| 9- SHEET A3.00: SPECIFY SIZE OF ATTIC ACCESS. SEC. |
| R807.1 FBC-RESIDENTIAL. |
| |
| 10- SHEET S1.00: |
| A) FIRST FLOOR FOUNDATION PLAN FOOTPRINT BY THE ENTRY |
| AREA AND FRONT PORCH DOESN'T MATCH FOOTPRINT SHOWN ON |
| THE FIRST FLOOR PLAN ON SHEET A3.00. REVISE AS REQUIRED |
| TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) REVISE LOCATION OF VERTICAL REINFORCEMENT AT ENTRY |
| DOOR. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| FRONT PORCH COLUMNS AND FOOTINGS. FOOTER DETAIL #3 |
| DOESN'T MATCH INFORMATION SHOWN ON THE FRONT PORCH |
| AREA. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| D) SECOND FLOOR FOUNDATION PLANS IS MISSING INFORMATION |
| FOR FRONT PORCH. SEE EXTERIOR ELEVATIONS. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 11- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| THE SOFFIT CONSTRUCTION AS SHOWN ON SHEET S3.00 ON THE |
| CUT SECTION DETAIL. SPECIFY ALL FRAMING MEMBERS AND |
| FASTENERS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| ONE HOUR FIRE RATED ASSEMBLY AT UNDERSIDE OF THE SOFFIT |
| AS REQUIRED BY TABLE R302.1(1) FBC-RESIDENTIAL. |
| |
| 12- SHEET S3.00: PROVIDE COMPLETE FRAMING PLANS, |
| DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| FRONT PORCH. CLEARLY SPECIFY ALL COLUMNS, BEAMS, ROOF |
| DECK, ETC. NOTE: 1ST FLOOR ROOF PLAN/FLOOR JOIST PLAN |
| SHOWS A HEADER THAT LOOKS LIKE IS FLOATING ON THE AIR. |
| HOW IS THIS HEADER SUPPORTED?. REVISE AS REQUIRED. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| 13- SPECIFY GARAGE ROOF PITCH. SEC. R905.11 |
| FBC-RESIDENTIAL. |
| |
| 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| GARAGE AND FRONT PORCH ROOF DRAINAGE SHOWING COMPLIANCE |
| WITH SEC. R903.4 AND SEC. R903.4.1 FBC-RESIDENTIAL. |
| SPECIFY ALL DRAINS, SCUPPERS AND OVERFLOW DRAIN, |
| SCUPPERS. CLEARLY SHOW LOCATION, SIZES, ETC. |
| |
| 15- BASE FLASHING DETAIL FOR WALL SUPPORTED DECK ON |
| SHEET S4.00 IS NOT LEGIBLE. THE LETTERING IS TOO SMALL. |
| PROVIDE DETAIL WITH LARGER LETTERING. SEC. 107.2.1.4 |
| CITY AMENDMENTS. NOTE: COORDINATE WITH ACTUAL ROOFING |
| PRODUCT APPROVAL SUBMITTED TO AVOID CONFLICTS/DELAYS. |
| |
| 16- GARAGE WALL SECTION DETAIL ON SHEET S4.00: |
| A) BEAM SPECIFICATIONS ARE NOT CLEAR. PROVIDE CLEAR |
| DETAIL SHOWING HOW THE BEAM IS BUILT WITH THE FOLLOWING |
| SPECIFICATIONS: "FORM & POUR CONCRETE LINTEL W/4#5 |
| REBARS CONTINUOUS & REINFORCED WITH (4)-#5 REBAR X |
| CONT. (PLACE (4)-#5 L-BAR W/24" LEGS AT ALL CORNERS. |
| NOTE: LINTELS TO BE PRE-CAST". SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B) PROVIDE DETAILS AND SPECIFICATIONS FOR THE TIE BEAM |
| T AT THE TOP OF PARAPET WALL. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| ROOF SHEATHING. SPECIFY TYPE, THICKNESS, FASTENERS, |
| ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 17- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| DRAFSTOPPING ON THE SECOND FLOOR AS REQUIRED BY SEC. |
| R302.12 FBC-RESIDENTIAL. SPECIFY LOCATION AND MATERIALS |
| TO BE USED. |
| |
| 18- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| FIREBLOCKING AS REQUIRED BY SEC. R302.11 |
| FBC-RESIDENTIAL. SPECIFY LOCATION AND MATERIALS TO BE |
| USED. |
| |
| 19-PROPOSED SITE PLAN ON SHEET C1.00 DOESN'T MATCH |
| SURVEY SUBMITTED. SETBACKS FOR GARAGE AND MAIN HOUSE |
| DON'T MATCH.REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 20- ENERGY CALCULATIONS SUBMITTED: |
| A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM. PROVIDE CORRECT NAME OF BUILDER AND SPECIFY |
| PERMIT OFFICE AND JURISDICTION NUMBER (604700). SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| B) NUMBER OF BEDROOMS IS INCORRECT. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| C) CALCULATIONS NEED TO BE DONE FOR THE ACTUAL |
| ORIENTATION OF THE BUILDING NOT FOR THE WORST CASE |
| SCENARIO. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| D) COOLING INFORMATION ON ITEM #12 IS INCORRECT. IT CAN |
| NOT BE 18.0 KBTU/HR FOR A 2807 CONDITIONED FLOOR AREA. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). COORDINATE WITH THE |
| EQUIPMENT SIZING CALCULATIONS. |
| |
| E) HEATING INFORMATION ON ITEM #13 IS INCORRECT. IT CAN |
| NOT BE 21.5 KBTU/HR FOR A 2807 CONDITIONED FLOOR AREA. |
| REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). COORDINATE WITH THE |
| EQUIPMENT SIZING CALCULATIONS. |
| |
| F) ITEM #15 IS TAKING THE CEILING FAN AND CROSS |
| VENTILATION CREDITS. NOTE: PLANS DON'T PROVIDE ANY |
| SPECIFICATIONS TO TAKE THESE CREDITS INTO |
| CONSIDERATION. COORDINATE WITH ENGINEER OF RECORD. IF |
| CREDITS ARE GOING TO BE TAKEN, THEN NEED TO PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE |
| WITH SEC. SEC. R405.7.6 AND SEC. R405.7.4 FBC-ENERGY |
| CONSERVATION. |
| |
| G) THE ENERGY CALCULATIONS NEED TO BE CERTIFIED AT THE |
| BOTTOM BY THE OWNER OR BY THE LEGALLY DESIGNATED AGENT |
| AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| CALCULATIONS SUBMITTED HAVE THE NAME OF THE PERSON WHO |
| PREPARED THE CALCULATIONS AS THE OWNER OR AGENT. IS |
| THIS PERSON LEGALLY DESIGNATED BY THE OWNER TO SIGN ON |
| HIS/HER BEHALF?. PROVIDE DOCUMENT SHOWING THAT HE'S |
| LEGALLY DESIGNATED OR OWNER TO PROVIDE NAME AND |
| SIGNATURE AT BOTTOM OF FORM. |
| |
| H) REVISE DOORS INFORMATION. CLEARLY SPECIFY WHERE ARE |
| THE INSULATED DOORS LOCATED . PLANS DON'T SHOW ANY |
| INSULATED DOOR. DOORS WITH GLAZING NEED TO BE |
| INCORPORATED IN TO THE WINDOW AREAS AS REQUIRED BY SEC. |
| R405.5.3.3 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED. |
| |
| I) PROVIDE THE EPL DISPLAY CARD COMPLETED BY THE |
| BUILDER AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| J) PROVIDE THE MANDATORY REQUIREMENTS PAGES AS REQUIRED |
| BY SEC. R405.4.2 FBC-ENERGY CONSERVATION. |
| |
| NOTE: LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR |
| AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS |
| WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT |
| USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED DRAWING AND INSERT NEW |
| DRAWING. DON'T STAPLE OLD DRAWINGS TO PLANS. SUBMITT |
| OLD DRAWINGS FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |