Plan Review Notes
Plan Review Notes For Permit 16120927
Permit Number 16120927
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-29 08:51:141) INDICATE ON SPECIFICATIONS THE SIZE OF THE GAS
 HEATER (BTU LOAD) THAT IS BEING INSTALLED.
 2) IS THIS POOL HEATER CONNECTING TO EXISTING PIPING OR
 IS A NEW GAS SYSTEM OR PIPING BEING INSTALLED? INDICATE
 SUCH ON THE DOCUMENTS.IF A NEW SYSTEM, COMPLY WITH THE
 FOLLOWING:
  
 1.) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD
 ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 4.) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
  
 5) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 6) IF THIS IS A REPLACEMENT OF AN EXISTING POOL HEATER,
 INDICATE THE BTU LOAD OF THE EXISTING POOL HEATER BEING
 REPLACED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: A SEPARATE GAS PERMIT APPLICATION IS REQUIRED
 FROM A PROPERLY LICENSED GAS CONTRACTOR FOR THE GAS
 CONNECTIONS TO THE POOL HEATER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  