Plan Review Notes
Plan Review Notes For Permit 16120922
Permit Number 16120922
Review Stop G
Sequence Number 3
Notes
Date Text
2017-01-17 13:55:321) THE REVISED PLANS NOW SHOW CSST IN THE CRAWL SPACE
 BUT YOU HAVE NOT PROVIDED THE SIZING TABLE USED FOR THE
 CSST. A COMPLETE REVIEW CANNOT BE DONE WITHOUT KNOWING
 WHICH SIZING TABLE IS BEING USED. 2014 FBC-FUEL GAS
 SEC.402.3.
 2) SUPPLY THE CORRESPONDING EHD FOR THE CSST SIZES.
 3) THE SIZE OF THE 3/4 INCH LOW PRESSURE LINE TO THE
 POOL HEATER SHALL BE 1 INCH PER TABLE 402.4 (2) .
 MAXIMUM BTU LOAD ON 3/4 INCH GALVANIZED PIPE IS 360
 MBTU.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  