Plan Review Notes For Permit 16120922 |
Permit Number |
16120922 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-01-17 13:55:32 | 1) THE REVISED PLANS NOW SHOW CSST IN THE CRAWL SPACE | | BUT YOU HAVE NOT PROVIDED THE SIZING TABLE USED FOR THE | | CSST. A COMPLETE REVIEW CANNOT BE DONE WITHOUT KNOWING | | WHICH SIZING TABLE IS BEING USED. 2014 FBC-FUEL GAS | | SEC.402.3. | | 2) SUPPLY THE CORRESPONDING EHD FOR THE CSST SIZES. | | 3) THE SIZE OF THE 3/4 INCH LOW PRESSURE LINE TO THE | | POOL HEATER SHALL BE 1 INCH PER TABLE 402.4 (2) . | | MAXIMUM BTU LOAD ON 3/4 INCH GALVANIZED PIPE IS 360 | | MBTU. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | |
|