Plan Review Notes For Permit 16120922 |
Permit Number |
16120922 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-10 06:35:42 | 1) SHT. G-2 - SHOW THE PIPE SIZE OF THE UNDERGROUND PE | | PIPE WHERE IT TRANSITIONS FROM THE 1 1/4" GALVANIZED | | LINE. IF IT IS 3/4 INCH PE PIPE IT IS UNDERSIZED PER | | 2014 FBC FUEL GAS TABLE 402.4 (22). A MAXIMUM OF | | 860,000 BTU'S CAN BE SUPPLIED BY A 3/4 INCH PE PIPE AT | | 133 FEET( MUST USE THE 150 FT. ROW). THE PLANS NOTE THE | | TOTAL LOAD AS 1177 MBTU/H. | | 2) SHOW THE PIPE SIZE OF THE SECTION OF 2 PSI PE | | UNDERGROUND PIPE THAT SUPPLIES THE POOL HEATER AND | | TANKLESS WATER HEATER # 3. ( IT IS THE SECTION BETWEEN | | THE TWO "TEE" FITTINGS). | | 3) SIZE THE 2 PSI BRANCH LINE TO THE BBQ.IS THIS | | GALVANIZED OR PE? | | 4) SIZE THE 2 PSI RISER TO THE TANKLESS WATER HEATER | | #1. | | 5) SIZE THE 2 PSI RISER TO THE COOKTOP AND DRYER. | | 6) SIZE THE 2 PSI RISER TO THE TANKLESS WATER HEATER | | #2. | | 7) SHT. G-2 - CLEARLY INDICATE ON THE RISER DIAGRAM | | WHERE THE PIPING BEGINS IN THE CRAWL SPACE. IT APPEARS | | TO OCCCUR BY TANKLESS WATER HEATER #1. CLARIFY. | | 8) SHOW THE DISTANCE FROM THE STEP DOWN REGULATOR TO | | THE APPLIANCE. THIS DISTANCE MUST BE SUPPLIED TO ENSURE | | CORRECT SIZING OF THE LOW PRESSURE SYSTEM. EACH ONE IS | | DIFFERENT SO DO NOT SUPPLY A TYPICAL DISTANCE FOR ALL | | OF THEM. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|