Plan Review Notes
Plan Review Notes For Permit 16120922
Permit Number 16120922
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-31 05:52:241)THE SUBMITTED PLAN SHEETS CONTAIN AN ARCHITECT'S
 TITLE BLOCK AND COPY OF HIS SEAL. THESE PLANS MUST BE
 SIGNED AND SEALED BY THE ARCHITECT PER THE FL. ADMIN.
 CODE RULE 61G1-16.001.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER AND
 THE FIREPLACE. SHOW THE DIMENSIONS (LXWXH) OF THE
 LAUNDRY ROOM AND THE FAMILY ROOM ON THE PLAN. 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407. THE VENT BLOCKS SHALL BE ADEQUATE TO AUPPLY THE
 REQUIRED AMOUNT OF COMBUSTION AIR.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY ( MP
 REGULATOR ) TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1
 OR 2014 FBC-RES. SEC. G 2413.3. THIS IS REQUIRED TO
 CHECK THE SIZES ON THE LOW-PRESSURE SYSTEM.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 TANKLESS WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS.THE NOTES ON
 THE SURVEY ARE ILLEGIBLE WITH ALL THE GAS INFORMATION
 THAT HAS BEEN WRITTEN ON IT. SUBMIT AN
 ENLARGED/EXPANDED SURVEY WITH THE REQUIRED INFORMATION
 ON IT.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW