2016-12-31 05:52:24 | 1)THE SUBMITTED PLAN SHEETS CONTAIN AN ARCHITECT'S |
| TITLE BLOCK AND COPY OF HIS SEAL. THESE PLANS MUST BE |
| SIGNED AND SEALED BY THE ARCHITECT PER THE FL. ADMIN. |
| CODE RULE 61G1-16.001. |
| 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE DRYER AND |
| THE FIREPLACE. SHOW THE DIMENSIONS (LXWXH) OF THE |
| LAUNDRY ROOM AND THE FAMILY ROOM ON THE PLAN. 2014 |
| FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G |
| 2407. THE VENT BLOCKS SHALL BE ADEQUATE TO AUPPLY THE |
| REQUIRED AMOUNT OF COMBUSTION AIR. |
| 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY ( MP |
| REGULATOR ) TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1 |
| OR 2014 FBC-RES. SEC. G 2413.3. THIS IS REQUIRED TO |
| CHECK THE SIZES ON THE LOW-PRESSURE SYSTEM. |
| 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| TANKLESS WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS.THE NOTES ON |
| THE SURVEY ARE ILLEGIBLE WITH ALL THE GAS INFORMATION |
| THAT HAS BEEN WRITTEN ON IT. SUBMIT AN |
| ENLARGED/EXPANDED SURVEY WITH THE REQUIRED INFORMATION |
| ON IT. |
| |
| |