Plan Review Notes For Permit 16120916 |
Permit Number |
16120916 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-03 08:17:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO. | | 12-0716.18 FOR THE TAMKO MODIFIED BITUMEN ROOF SYSTEM | | HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF. THIS DOES | | NOT MEET THE REQUIRED UPLIFT PRESSURES FOR THE | | PERIMETER AND CORNER AREAS. SUBMIT TWO SETS OF SIGNED | | AND SEALED RAS 117 CALCULATIONS FOR ENHANCED FASTENING | | AS REQUIRED BY LIMITATION NUMBER 7 ON PAGE 15 OF THE | | PRODUCT APPROVAL. FBC 107.2.1.3 |
|