2017-06-01 17:11:353RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16120880
 6/1/17
  
 RESULTS: DENIED.
  
 COMMENTS FROM THE 2ND REVIEW PRINTED BELOW STILL EXIST.
  
 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, PROVIDE DUCT
 SMOKE DETECTORS IN THE RETURN AIR SYSTEM OF AC-1 & 2.
  
 2) THE LOUVERED DOOR ENCLOSING THE MECHANICAL CLOSET
 FOR AC-1 MUST BE NON-COMBUSTIBLE PER SECTION C403.2.7.2
 FBC-14 ENERGY CONSERVATION, AND SECTION 602.2.1 FBC-14
 MECHANICAL.
  
 3) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA FOR THE
 LOUVER- #16-0201.03.
  