Plan Review Notes
Plan Review Notes For Permit 16120880
Permit Number 16120880
Review Stop M
Sequence Number 2
Notes
Date Text
2017-03-28 14:01:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16120880
 3/28/17
  
 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, PROVIDE DUCT
 SMOKE DETECTORS IN THE RETURN AIR SYSTEM OF AC-1 & 2.
  
 2) THE LOUVERED DOOR ENCLOSING THE MECHANICAL CLOSET
 FOR AC-1 MUST BE NON-COMBUSTIBLE PER SECTION C403.2.7.2
 FBC-14 ENERGY CONSERVATION, AND SECTION 602.2.1 FBC-14
 MECHANICAL.
  
 3) SUBMIT THE NOA #14-0414.08 FOR THE LOUVER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  