Plan Review Notes For Permit 16120880 |
Permit Number |
16120880 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-03-28 14:01:33 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16120880 | | 3/28/17 | | | | 1) AS PREVIOUSLY NOTED IN THE 1ST REVIEW, PROVIDE DUCT | | SMOKE DETECTORS IN THE RETURN AIR SYSTEM OF AC-1 & 2. | | | | 2) THE LOUVERED DOOR ENCLOSING THE MECHANICAL CLOSET | | FOR AC-1 MUST BE NON-COMBUSTIBLE PER SECTION C403.2.7.2 | | FBC-14 ENERGY CONSERVATION, AND SECTION 602.2.1 FBC-14 | | MECHANICAL. | | | | 3) SUBMIT THE NOA #14-0414.08 FOR THE LOUVER. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|