2017-01-24 09:43:04 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT IS CALLING |
| THIS PROJECT AN A-2 IT SHOULD BE AN A-3 PLEASE CLARIFY |
| . PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. ARE THE RESTROOMS IN THE TENNIS CENTER SERVING THE |
| TENNIS COURTS OCCUPANT LOAD IF SO INCLUDE IT IN THE |
| FIXTURE COUNT IF NOT SHOW LOCATION OF BATHROOMS SERVING |
| TENNIS COURTS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHOW COMPLIANCE FOR TOILET PAPER DISPENSER PER FBC |
| ACC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 4. SHOW COMPLIANCE FOR TOILET . PER FBC ACC 604.2 |
| LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| RIGHT-HAND APPROACH. |
| |
| 5. SHT. A-1.4.02 GENERAL NOTE AND ADA NOTES ARE UNCLEAR |
| SOME OF THE WORDS ARE OVERLAPPING PLEASE CLARIFY. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 6. SHT. A-1.4.03 NOTES REFERENCE 2010 ADA AND 2012 FABC |
| THIS PROJECT SHALL BE DESIGNED UNDER FBC ACC 2014 5TH |
| ADDITION. PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7. SHT. 1.4.04 IS MISSING WORDS AND FIGURE NUMBERS FOR |
| EXAMPLE 403.5.2 CLEAR WIDTH AT ?, 404 DOORS DOORWAYS |
| AND ? AND THE FIGURES ARE MISSING SEC NUMBERS PLEASE |
| CLARIFY . PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. A WATER FOUNTAIN IS REQUIRED PER FBC PL TABLE 403.1 |
| AND SHALL COMPLY WITH FBC PL |
| [B] 410.2 MINIMUM NUMBER. |
| WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| AND FBC ACC 602 |
| |
| 9. ALL LAVATORY'S ARE REQUIRED TO HAVE TEMPERED WATER. |
| PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| FACILITIES. |
| TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 10. PLEASE PROVIDE NOT ON THE PLAN FOR SEPARATE PERMIT |
| REQUIRED FOR THE BACKFLOW AT THE METER. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 11. SHUT OFF VALVES ARE REQUIRED ON THE HW FEEDS TO |
| EACH BATHROOM. PER FBC PL 606.1(5) |