2017-01-09 14:39:44 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #16120880 |
| 1/9/17 |
| |
| 1) THE 21 PERSON OCCUPANT DENSITY AND 163 CFMS OF O/A |
| AIR DOES NOT APPEAR TO BE CONSISTENT WITH THE USE OF |
| THE ROOM BASED ON THE OCCUPANT LOAD OF 151 INDICATED ON |
| THE LIFE SAFETY PAGES. CLARIFY WHAT THE ROOM IS TO BE |
| USED FOR AND SELECT THE CORRESPONDING VENTILATION RATE |
| LISTED IN TABLE 403.3 OR ASHRAE 62.1-2010. |
| |
| 2) M-1.3.01: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| RETURN AIR SYSTEMS OF AC- 1 & 2 PER SECTION 606.2.1. |
| PLEASE SHOW THE LOCATIONS OF THE DEVICES ON THE PLANS |
| UNLESS IT CAN BE VERIFIED BY MANUFACTURER'S |
| SPECIFICATIONS THAT THE SYSTEMS CANNOT EXCEED 2000 CFMS |
| OF SUPPLY AIR. |
| |
| 3) M-1.3.01: PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR |
| THE O/A TO AC-2 PER SECTION C403.2.4.4 FBC-14 ENERGY |
| CONSERVATION. THE CURRENT PLAN SHOWS A "BD" NOT AN "MD" |
| TO BE LOCATED IN THE DUCT. |
| |
| 4) M-1.3.01: PROVIDE THE FLEX DUCT SIZES. |
| |
| 5) M-1.3.01: PROVIDE A FL. PRODUCT APPROVAL OR |
| MIAMI-DADE NOA FOR THE O/A AND EXHAUST LOUVERS. |
| |
| 6) M-3.0.00: THE AC SCHEDULE IS INDICATING "OFFICES" AS |
| THE AREAS SERVED WHICH DOES NOT APPEAR TO BE CONSISTENT |
| WITH THE PLANS. |
| |
| 7) PROVIDE FIRE DAMPER INSTALLATION DETAILS. |
| |
| 8) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION FOR |
| THE EXTERIOR CODENSERS- SECTION 301.15 |
| |