2017-01-09 14:39:441ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120880
 1/9/17
  
 1) THE 21 PERSON OCCUPANT DENSITY AND 163 CFMS OF O/A
 AIR DOES NOT APPEAR TO BE CONSISTENT WITH THE USE OF
 THE ROOM BASED ON THE OCCUPANT LOAD OF 151 INDICATED ON
 THE LIFE SAFETY PAGES. CLARIFY WHAT THE ROOM IS TO BE
 USED FOR AND SELECT THE CORRESPONDING VENTILATION RATE
 LISTED IN TABLE 403.3 OR ASHRAE 62.1-2010.
  
 2) M-1.3.01: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF AC- 1 & 2 PER SECTION 606.2.1.
 PLEASE SHOW THE LOCATIONS OF THE DEVICES ON THE PLANS
 UNLESS IT CAN BE VERIFIED BY MANUFACTURER'S
 SPECIFICATIONS THAT THE SYSTEMS CANNOT EXCEED 2000 CFMS
 OF SUPPLY AIR.
  
 3) M-1.3.01: PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR
 THE O/A TO AC-2 PER SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION. THE CURRENT PLAN SHOWS A "BD" NOT AN "MD"
 TO BE LOCATED IN THE DUCT.
  
 4) M-1.3.01: PROVIDE THE FLEX DUCT SIZES.
  
 5) M-1.3.01: PROVIDE A FL. PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE O/A AND EXHAUST LOUVERS.
  
 6) M-3.0.00: THE AC SCHEDULE IS INDICATING "OFFICES" AS
 THE AREAS SERVED WHICH DOES NOT APPEAR TO BE CONSISTENT
 WITH THE PLANS.
  
 7) PROVIDE FIRE DAMPER INSTALLATION DETAILS.
  
 8) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION FOR
 THE EXTERIOR CODENSERS- SECTION 301.15
  