2017-01-09 08:35:45THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.0.02 - THE IS AN INCORRECT REFERENCE TO
 THE FIRE CODE; THE BROWARD COUNT ADMENDMENTS IS NOT
 APPLICABLE WITHIN THEI JURISDICTION.
  
 PLEASE REMOVE THE REFERENCE AND ENSURE NO CONFLICTS.
  
  
  
 2) SHEET A 1.2.01 - THE LIFE SAFETY NOTES INDICATE
 REFERENCES TOA FIRE SPRINKLER AND FIRE ALARM. THESE
 NOTES ARE CONFUSING AS TO THEM BEING INSTALLED OR NOT.
  
 PLEASE CLARIFY AND REMOVE ANY REFERENCES IF NOT
 PROPOSED.
  
  
  
 3) SHEET 1.2.01 & 2.1.02 - THERE ARE INDICATIONS OF AN
 EXIT, # 2, LEADING TO THE TERRACE; HOWEVER, THE TERRACE
 INDICATES RALINGS WITH NO EXIT VOID OR GATE.
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
  
 PLEASE CLARIFY AND CORRECT.
  
  
  
 4) SHEET 1.2.01 & 2.1.02 - THE ARE TWO EXITS INDICATED
 FROM THE ASSEMBLY ROOM WITH A SEPARATION OF 17.5 FT.
 THE EXITS ARE REQUIRED TO BE SEPARATED BY A MINIMUM OF
 HALF THE AREA DIMENSION.
  
  
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS REQUIRED FROM A BUILDING OR PORTION
 THEREOF, SUCH EXITS, EXIT ACCESSES, OR EXIT DISCHARGES
 SHALL BE REMOTELY LOCATED FROM EACH OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR
 OTHER EMERGENCY CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED
 IN 7.5.1.3.3 THROUGH 7.5.1.3.5.
  
  
 PLEASE REVIEW, CLARIFY AND/OR CORRECT.
  
  
  
 5) SHEET A 2.1.02 - THERE ARE INDICATIONS OF LIGHT
 WIEGHT TRUSS DESIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PLEASE PROVIDE A NOTE FOR THE APPLICABLE SIGNAGE AT THE
 FRONT ENTRANCE.
  
  
  
 6) SHEET 6.2.01 - THERE IS A LABEL INDICATION WITHIN
 THE DOOR SCHEDULE OF A C45; HOWEVER, THERE IS NO
 CALL-OUT INDICATING/IDENTIFYING WHAT IT IS.
  
 PLEASE INDICATE WHAT C45 IS?
  
  
  
 7) SHEET A 6.2.01 - IN THE DOOR SCHEDULE FOR DOOR 104,
 THAT SERVES ROOM 151, THERE IS NO EXIT DEVICE IN THE
 COMMENT SECTION.
  
 PLEASE CORRECT.
  
  
  
 8) SHEET A 6.2.01 - THE IS A NOTE ON ALL THE EXIT DOORS
 OF A "CYLINDER KEY SYSTEM". PER NFPA 101, CHAPTER 7,
 MEANS OF EGRESS
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE. INDICATE IF THE DOORS
 WILL BE EQUIPPED WITH ANY LOCK/LATCH. IF THE DOORS WILL
 BE EQUIPPED WITH A LOCK/LATCH, INDICATE HOW THE
 LOCK/LATCH WILL BE RELEASED FROM THE EGRESS SIDE OF THE
 DOOR.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS
 AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY
 OPERATED UNDER ALL LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN
 THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING
 OPERATION, UNLESS OTHERWISE SPECIFIED IN
 7.2.1.5.10.3, 7.2.1.5.10.4, OR 7.2.1.5.10.6.
  
  
 FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 PLEASE ENSURE THAT EACH LOCKING DEVICE/SYSTEM COMPLIES
 WITH THE ABOVE REQUIREMENTS.
  
  
  
 9) SHEET E 0.0.01 - THE LEGEND IS INDICATING FA
 DEVICES. THESE SYMBOLS/COMMENTS ARE CONFUSING AND ARE
 IN ADDITION TO # 2 ABOVE.
  
 IF THERE IS NO FIRE ALARM PROPOSED, NO REFENCES SHOULD
 BE INDICATED AND/OR REMOVED.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  