2017-01-07 03:10:57 
 1) A PLAN REVIEW COULD NOT BE PERFORMED BEACAUSE THE
 SIZING TABLE BEING USED IS UNKNOWN.SUBMIT TWO COPIES OF
 THE SIZING TABLES USED IN THE DESIGN FOR THIS GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM THE GAS CODE THAT WERE USED IN
 THE DESIGN OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G
 2413.3.
 2) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY,
 (GAS METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4) SHUTOFF VALVES ARE REQUIRED IMMEDIATELY AHEAD OF
 EACH MP REGVULATOR. 2014 FBC - FUEL GAS SEC.409.4.
  
 NOTE : DO NOT RESUBMIT THESE PLANS UNTIL ALL OF THE
 PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. IF THE PLANS
 GET REJECTED AGAIN FOR ANY REPEAT COMMENT, A FEE OF
 FOUR TIMES THE AMOUNT OF THE PROPORTION ATTRIBUTED TO
 PLANS REVIEW SHALL BE PAID PER FL. STATUTE 553.80 (2)
 (B).
  
  