Date |
Text |
2017-01-07 05:12:40 | |
| 1) A PLAN REVIEW COULD NOT BE PERFORMED BEACAUSE THE |
| SIZING TABLE(S) BEING USED IS UNKNOWN.SUBMIT TWO COPIES |
| OF THE SIZING TABLES USED IN THE DESIGN FOR THIS GAS |
| SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING |
| THE SIZING TABLES FROM THE GAS CODE THAT WERE USED IN |
| THE DESIGN OF THIS SYSTEM. FGC SEC.402.3, FBCR SEC. G |
| 2413.3. |
| 2) SHOW THE TOTAL DISTANCE FROM THE POINT OF DELIVERY, |
| ( GAS METER / MP REGULATOR ) TO THE MOST REMOTE OUTLET |
| IN THE BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL |
| GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| 3) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| 4) SUBMIT AN EXPANDED GAS RISER THAT CLEARLY SHOWS THE |
| PIPE SIZES, ETC. WPB AMEND. TO FBC SEC. 107.2.1. SOME |
| PIPE SIZES ARE STILL DIFFICULT TO READ. |
| 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE |
| WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| 6) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. THE GAS RISER |
| APPEARS TO SHOW THE SHUTOFF VALVES DOWNSTREAM OF THE |
| REGULATORS. |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1, 2014 |
| FBC-FUEL GAS SEC.410.1, 410.2. |
| 8) SHOW THE PIPE SIZE OF THE PE PIPE TO THE FIRE PIT. |
| 9) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS (IF APPLICABLE) PER 2014 |
| FBC-FUEL GAS SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G |
| 2426. |
| |
| NOTE : DO NOT RESUBMIT THESE PLANS UNTIL ALL OF THE |
| PLAN REVIEW COMMENTS HAVE BEEN ADDRESSED. IF THE PLANS |
| GET REJECTED AGAIN FOR ANY REPEAT COMMENT, A FEE OF |
| FOUR TIMES THE AMOUNT OF THE PROPORTION ATTRIBUTED TO |
| PLANS REVIEW SHALL BE PAID PER FL. STATUTE 553.80 (2) |
| (B). |
| |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |