2016-12-27 19:06:19 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE WRONG CODE EDITION IS REFERENCED ON THE PLANS. |
| THIS SCOPE OF WORK IS REQUIRED TO COMPLY WITH THE 2014 |
| FLORIDA BUILDING CODE. |
| |
| 2) THE ASSEMBLY NUMBER SPECIFIED ON THE DRAWING U494 IS |
| FOR A 2-1/2" 25 MSG STEEL FRAME WALL AND THE DRAWING |
| SPECIFIES A 3-5/8" 18 MSG STEEL FRAME WALL. IN ORDER TO |
| ACHIEVE THE RATING THE ASSEMBLY HAS TO BE CONSISTENT |
| WITH THE LISTING. FBC 107.2.1 |
| |
| 3) THE DRAWING IS NOT CLEAR AS TO WHICH WALLS ARE TO |
| HAVE THE ONE HOUR FIRE RESISTANCE RATING. ALL OF THE |
| NEW WALLS IN THE ATTIC ARE MARKED THE SAME. FBC 107.2.1 |
| |
| 4) SHEET A.03 OF THE PLANS THAT ARE ON FILE, INDICATE |
| THAT THE WALLS THAT SEPARATE THE GARAGE FROM THE LIVING |
| SPACE HAS A PORTION THAT IS MASONRY AND THE REST IS |
| 3-5/8" METAL FRAMING. THE WALL ALSO HAS A JOG IN IT AND |
| IS NOT STRAIGHT AS SHOWN IN YOUR DRAWING. FBC 107.2.1 |
| |
| 5) THE ATTIC WALL SECTION SPECIFIES HOW TO ATTACH IT TO |
| THE METAL STUD WALL BELOW. HOWEVER, IT DOES NOT SPECIFY |
| THE ATTACHMENT TO THE MASONRY WALL. FBC 107.2.1 |
| |
| 6) THE TRUSS PLAN ON FILE INDICATES THAT THE BOTTOM |
| CORD HAS A NON-CONCURRENT LIVE LOAD OF 10 PSF. THIS |
| UNINHABITABLE ATTIC AREA IS REQUIRED TO HAVE A 20 PSF |
| LIVE LOAD IF IT IS USED FOR LIMITED STORAGE. SUBMIT A |
| SET OF THE TRUSS DRAWINGS FOR THIS AREA TO VERIFY THE |
| BOTTOM CORD LIVE LOAD. FBC-R 301.5 |
| |
| |
| |