Plan Review Notes For Permit 16120795 |
Permit Number |
16120795 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-06 13:24:54 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PLEASE PROVIDE AN ELECTRICAL SITE PLAN SHOWING THE | | LOCATION OF THE SITE LIGHTING. SHOW CIRCUIT NUMBER | | FEEDING SITE LIGHTING. PROVIDE A FIXTURE SCHEDULE AND | | PANEL BOARD SCHEDULE ASSOCIATED WITH THE SITE LIGHTING. | | 2. ADD A GENERAL NOTE TO PROVIDE COMPLIANCE PER FBC EC | | 405.7.4- COMPLETION DOCUMENTS PER CODE SECTION. FBC EC | | 405.7.3- VOLTAGE DROP NEW FEEDERS AND BRANCH CIRCUITS | | AND AUTOMATIC CONTROLS. | | 3. PROVIDE A NOTE TO MAINTAIN CONDUIT BURIAL DEPTH PER | | NEC 300.5 REQUIREMENTS. | | 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|