2017-03-06 13:24:54INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE AN ELECTRICAL SITE PLAN SHOWING THE
 LOCATION OF THE SITE LIGHTING. SHOW CIRCUIT NUMBER
 FEEDING SITE LIGHTING. PROVIDE A FIXTURE SCHEDULE AND
 PANEL BOARD SCHEDULE ASSOCIATED WITH THE SITE LIGHTING.
 2. ADD A GENERAL NOTE TO PROVIDE COMPLIANCE PER FBC EC
 405.7.4- COMPLETION DOCUMENTS PER CODE SECTION. FBC EC
 405.7.3- VOLTAGE DROP NEW FEEDERS AND BRANCH CIRCUITS
 AND AUTOMATIC CONTROLS.
 3. PROVIDE A NOTE TO MAINTAIN CONDUIT BURIAL DEPTH PER
 NEC 300.5 REQUIREMENTS.
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  