Plan Review Notes
Plan Review Notes For Permit 16120787
Permit Number 16120787
Review Stop P
Sequence Number 2
Notes
Date Text
2017-02-07 03:27:571) THE NARRATIVE RESPONSE TO PLUMBING REVIEW COMMENT #
 1 REFERS TO DETAIL 1 / SHT.A-1.01 FOR TOILET STALL
 DIMENSIONS. I COULD NOT FIND ANY OF THE REQUESTED
 INFORMATION/ DIMENSIONS ON DETAIL 1 / SHT. A-1.01 -
 CLARIFY.THE REQUIRED DIMENSIONS OF THE STANDARD TOILET
 STALLS SHALL BE A MINIMUM OF 30 INCHES WIDE BY 60
 INCHES DEEP PER 2014 FBC-PLUMBING SEC.405.3.1. 2ND
 REQUEST. NOTE: I FOUND A STALL DIMENSION ON SHT.A-4.01
 IN THE MEN'S TOILET ROOM. PLEASE NOTE THIS AS A TYPICAL
 DIMENSION FOR THE STANDARD STALLS.
 2) PLUMBING PLAN REVIEW COMMENT # 3 - THE NARRATIVE
 RESPONSE TO PLUMBING REVIEW COMMENT #3 REFERS TO
 DETAILS # 1 & # 2 ON SHT. A-1.01. DETAIL # 2 SHOWS A
 GAZEBO WITH NO PLUMBING FIXTURES IN IT SO I HAVE NO
 IDEA WHAT THIS RESPONSE APPLIES TO. DETAIL #1 DOES NOT
 PROVIDE THE REQUIRED INFORMATION. COMPLY WITH 2014
 FBC-ACCESS. SECS.604.5, 604.5.1, & 604.5.2.ALSO, REFER
 TO FIGURES 604.5.1 & 604.5.2.YOU WILL FIND THE
 REQUESTED INFORMATION IN THESE FIGURES. 2ND REQUEST.
 3) SHT. A-4.01 SHOWS THE HANDICAPPED ACCESSIBLE TOILET
 COMPARTMENTS AS 7'-0". THE MINIMUM WIDTH SHALL BE 7'-1"
 IF BUILT PERFECT. 7'-2" ALLOWS FOR CONSTRUCTION
 TOLERANCES.
 4) SHT.A-1.01 SHOWS A CLOUDED REFERENCE TO DETAIL # 3 /
 SHT. A-1.01. THERE IS NO SUCH DETAIL ON A-1.01. PLEASE
 REVISE WITH THE CORRECT SHEET, SHT. A-4.01.
 5) PLUMBING PLAN REVIEW COMMENT #5 - THE NARRATIVE
 RESPONSE REFERS TO DETAIL #3/SHT. A-2.01 FOR THE
 DRINKING FOUNTAINS. THERE IS NO DETAIL #3 ON THIS SHEET
 AND THE REQUIRED KNEE AND TOE CLEARANCES ARE NOT SHOWN.
 CLARIFY. 2ND REQUEST. SHOW THE REQUIRED KNEE AND TOE
 CLEARANCE FOR THE DRINKING FOUNTAIN PER 2014
 FBC-ACCESS. SEC.306. 2ND REQUEST. I FOUND THE DRINKING
 FOUNTAIN ELEVATIONS ON SHT. A-3.01. PLEASE CORRECT THE
 REFERENCE SHEET.
 6) SHT. E1.1 REFERS TO A LIFT STATION. SUBMIT COMPLETE
 DETAILS FOR THE LIFT STATION INCLUDING PIPING DETAILS,
 WHERE AND HOW THE STATION CONNECTS TO THE MAIN SANITARY
 SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.THE NARRATIVE
 RESPONSE STATES THAT THE CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT IS PERFORMING A REVIEW
 OF THE LIFT STATION THIS IS FINE BUT THE PLANS/ SPECS
 AND DETAILS MUST ALSO BE REVIEWED BY THE PLUMBING
 SECTION OF THE CONSTRUCTION SERVICES DIVISION AS THE
 2014 FBC-PLUMBING SEC.712 APPLIES TO THIS INSTALLATION
 AND THEREFORE MUST BE REVIEWED FOR COMPLIANCE. 2ND
 REQUEST.
 7) FLOOR PLANS SHOW A SERVICE/PUMP ROOM. SUBMIT DETAILS
 FOR THE PUMP & PIPING THAT WILL BE INSTALLED. PB AMEND.
 TO FBC SEC. 107.2.1.
 8) SHT. FSP - SITE PLAN KEY LISTS A TOTAL OF THREE
 DRINKING FOUNTAINS BUT ONLY THE DRINKING FOUNTAINS AT
 THE MAIN PAVILLION ARE SHOWN ON THE SANITARY AND WATER
 RISERS. CLARIFY.REFER TO THE DRINKING FOUNTAIN BY THE
 SHADE STRUCTURE AT THE PLAYGROUND.
 9) SHUTOFF VALVES SHALL BE INSTALLED ON ALL WALL
 HYDRANTS / HOSE BIBBS. 2014 FBC-PLUMBING SEC.606.2 (
 2).
 10) A FULL - OPEN VALVE SHALL BE INSTALLED ON THE WATER
 SUPPLY PIPE TO THE WATER HEATER. 2014 FBC-PLUMBING
 SEC.606.1 (8).
 11) IF THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER
 PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT OR TEMPERED WATER, A HOT
 WATER RECIRCUATING LINE SHALL BE REQUIRED. 2014
 FBC-PLUMBING SEC.607.2.
 12) THE APPROVED SITE PLAN AND SHT. C3.02 SHOW A SPLASH
 PAD AND A SHOWER. IF THESE WILL BE DONE UNDER A
 SEPARATE PERMIT PLEASE NOTE SUCH ON THE PLAN.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  