Plan Review Notes
Plan Review Notes For Permit 16120787
Permit Number 16120787
Review Stop P
Sequence Number 1
Notes
Date Text
2017-01-21 07:20:141) THE REQUIRED DIMENSIONS OF THE STANDARD TOILET
 STALLS SHALL BE A MINIMUM OF 30 INCHES WIDE BY 60
 INCHES DEEP PER 2014 FBC-PLUMBING SEC.405.3.1.
 2) SHT. A-4.01 & A-4.02 - THE GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE. 2014
 FBC-ACCESS. SEC. 609.4.
 3) THE PLACEMENT OF THE SIDE AND REAR GRAB BARS FOR THE
 WATER CLOSETS SHALL COMPLY WITH 2014 FBC-ACCESS.
 SEC.604.5, 604.5.1, 604.5.2.
 4) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF THE
 ACCESSIBLE TOILET STALLS.COMPLY WITH 2014 FAC SEC.604.
 5) SHOW THE REQUIRED KNEE AND TOE CLEARANCE FOR THE
 DRINKING FOUNTAIN PER 2014 FBC-ACCESS. SEC.306.
 6) INDICATE THE CAPACITY OF THE EXPANSION TANK ON THE
 PLANS.
 7)FLOOR PLANS SHOW A SERVICE/PUMP ROOM. SUBMIT DETAILS
 FOR THE PUMP & PIPING THAT WILL BE INSTALLED. PB AMEND.
 TO FBC SEC. 107.2.1.
 8) SHT. P-3 -SIZE ALL THE WET SECTIONS OF THE WASTE
 STACKS.
 9) THE FLOOR DRAINS LOCATED IN THE SERVICE/PUMP ROOM,
 THE WOMEN'S RESTROOM AND THE MEN'S RESTROOM APPEAR TO
 EXCEED THE MAXIMUM DISTANCE OF THE TRAP TO A VENT PER
 2014 FBC-PLUMBING TABLE 909.1.
 10) SHT. E1.1 REFERS TO A LIFT STATION. SUBMIT COMPLETE
 DETAILS FOR THE LIFT STATION INCLUDING PIPING DETAILS,
 WHERE AND HOW THE STATION CONNECTS TO THE MAIN SANITARY
 SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 11) PLEASE EXPLAIN HOW YOU ARRIVED AT THE NUMBER OF
 SANITARY FACILITIES REQD. FOR THIS TYPE OF OCCUPANCY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  