2017-01-24 07:27:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16120787
 1/24/17
  
 1) REFER TO SECTION 404.2 AND PROVIDE CODE COMPLIANT
 NATURAL VENTILATION CALCULATIONS FOR THE STORAGE ROOM,
 THE MEN/WOMEN'S RESTROOMS, AND THE SERVICE/PUMP ROOM.
  
 2) REFER TO SECTION 309.1 AND PROVIDE A SPACE HEATING
 SYSTEM FOR THE MAINTENANCE/STORAGE ROOM. PLEASE INCLUDE
 SYSTEM SIZING CALULATIONS PER SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
  
 3) PROVIDE DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE PER SECTION C101.2 AND C401.2.
  
 4) PROVIDE DETAILS FOR ATTACHMENT OF THE FANS AND FAN
 CURBS TO THE ROOF STRUCTURE- SECTION 301.15.
  
 5) SUBMIT A FL. PRODUCT APPROVAL AND/OR MIAMI-DADE NOA
 FOR THE WALL LOUVERS.
  