Plan Review Notes For Permit 16120787 |
Permit Number |
16120787 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-24 15:33:43 | 5100 NORTH HAVERHILL ROAD | | PERMIT #16120787 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PER NFPA 1 SECTION 8.2.3.1.1 APPROVED FIRE DEPARTMENT | | ACCESS ROADS AND FIRE HYDRANTS SHALL BE PROVIDED FOR | | EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING | | HEREAFTER CONSTRUCTED OR RELOCATED. A FIRE DEPARTMENT | | ACCESS ROAD SHALL EXTEND TO WITHIN 50 FEET OF AT LEAST | | ONE EXTERIOR DOOR THAT CAN BE OPENED FROM THE OUTSIDE | | AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE | | BUILDING. WHEN BUILDINGS ARE PROTECTED THROUGHOUT WITH | | AN APPROVED AUTOMATIC SPRINKLER SYSTEM THAT IS | | INSTALLED IN ACCORDANCE WITH NFPA 13, THE DISTANCE | | SHALL BE PERMITTED TO BE INCREASED TO 450 FEET. | | | | PROVIDE SEPARATE ADDRESSES OR BUILDING IDENTIFICATIONS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] |
|