2017-02-09 14:22:27 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16120785 (2) COVERED PAVILIONS |
| ADD: 5100 N. HAVERHILL RD. |
| CONT: STRATICON LLC |
| TEL: 772-210-0700 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: THURS. FEB. 09/2017 |
| ACTION: DENIED |
| |
| NOTE!!!!!!!! A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| 1) COMPLIED. |
| |
| 2) 2ND REQUEST. 2014 FLORIDA BUILDING CODE W 2014 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW |
| CRITERIA FOR BUILDINGS. |
| 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 8. STRUCTURAL REQUIREMENTS COLUMNS, BEAMS AN ROOF |
| FRAMING MEMBERS, COMPONENTS AND CLADDING. |
| |
| 3) 2ND REQUEST. MISSING: 2014 FBC-B 1609.1.2 PROTECTION |
| OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(D) ROOFING ASSEMBLIES. |
| |
| 4) 2ND REQUEST. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 5) 2ND REQUEST. SHEET S-1.01 GAZEBO FOUNDATION NOTES. |
| GAZEBO FOUNDATIONS ARE ESTIMATED SIZE AND MUST BE |
| VERIFIED USING SPECIALTY ENGINEER COLUMN BASE LOADS. |
| THIS REVIEW CYCLE THERE WERE NO PLANS NOR CALCULATIONS |
| FOR THE GAZEBO. WITHOUT ANY PLANS IT IS UNKNOWN IF THE |
| METAL DECK ROOFING IS STRUCTURAL, PURLIN SPACING IS |
| UNKNOWN NOR THE SIZE OF ANY HIPS AND OR IF THERE ARE |
| ANY HORIZONTAL STEEL BEAMS. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |