2017-01-18 15:54:56 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16120785 (2) COVERED PAVILIONS |
| ADD: 5100 N. HAVERHILL RD. |
| CONT: STRATICON LLC |
| TEL: 772-210-0700 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: WED. JAN. 18/2016 |
| ACTION: DENIED |
| |
| 1) THERE ARE 2 PAVILIONS AND ONE BUILDING WITH |
| RESTROOMS UNDER THE SAME ADDRESS. EACH BUILDING NEEDS |
| IT OWN ADDRESS FOR IDENTIFICATION DURING CONSTRUCTION |
| AS WELL AS FOR POLICE AND FIRE RESPONSE. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION OF THE PROJECT. |
| |
| 2) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 8. STRUCTURAL REQUIREMENTS COLUMNS, BEAMS AN ROOF |
| FRAMING MEMBERS, COMPONENTS AND CLADDING. |
| |
| 3) MISSING: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING ASSEMBLIES. |
| |
| 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) SHEET S-1.01 GAZEBO FOUNDATION NOTES. GAZEBO |
| FOUNDATIONS ARE ESTIMATED SIZE AND MUST BE VERIFIED |
| USING SPECIALTY ENGINEER COLUMN BASE LOADS. THIS REVIEW |
| CYCLE THERE WERE NO PLANS NOR CALCULATIONS FOR THE |
| GAZEBO. WITHOUT ANY PLANS IT IS UNKNOWN IF THE METAL |
| DECK ROOFING IS STRUCTURAL, PURLIN SPACING IS UNKNOWN |
| NOR THE SIZE OF ANY HIPS AND OR IF THERE ARE ANY |
| HORIZONTAL STEEL BEAMS. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |