Date |
Text |
2016-12-30 16:47:23 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| 1) FINAL APPROVAL IS PENDING SITE FIRE INSPECTIONS AND |
| VERIFICATION AS NECASSARY PRIOR TO EVENT START. |
2016-12-27 09:13:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE LOCATION OF THE GENERATORS DO NOT INDICATE ANY |
| SEPARATION DIMENSIONS OR EXHAUST LOCATIONS. PLEASE |
| PROVIDE THEM SHOWING COMPLOIANCE WITH THE BELOW NOTED |
| CODE. |
| |
| 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS. |
| 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS TURBINES |
| INSTALLATION. STATIONARY GENERATOR SETS SHALL BE |
| INSTALLED IN ACCORDANCE WITH NFPA 37, STANDARD FOR THE |
| INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES |
| AND GAS TURBINES, AND NFPA 70. |
| |
| 11.7.2.2 PORTABLE GENERATORS SHALL BE POSITIONED SO |
| THAT THE EXHAUST IS DIRECTED AS FOLLOWS: |
| (1) AT LEAST 5 FT (1.5 M) IN ANY DIRECTION AWAY FROM |
| ANY OPENINGS OR AIR INTAKES |
| (2) AWAY FROM THE BUILDING |
| |
| |
| |
| 2) A 1,000 KW GENERATOR IS LOCATED NEXT TO THE TENT. |
| PLEASE SEPARATE AND PROVIDE THE REQUIRED MINIMUM |
| DIMENSION NOTED BELOW AND FUEL CAPACITY AND TIME ON THE |
| PLAN. |
| |
| 25.1.12 GENERATORS. |
| 25.1.12.1 GENERATORS AND OTHER INTERNAL COMBUSTION |
| POWER SOURCES SHALL BE SEPARATED FROM TEMPORARY |
| MEMBRANE STRUCTURES AND TENTS BY A MINIMUM OF 5 FT (1.5 |
| M) AND SHALL BE PROTECTED FROM CONTACT BY FENCING, |
| ENCLOSURE, OR OTHER APPROVED MEANS. |
| 25.1.12.2 FUELING. FUEL TANKS SHALL BE OF ADEQUATE |
| CAPACITY TO PERMIT UNINTERRUPTED OPERATION DURING |
| NORMAL OPERATING HOURS. REFUELING SHALL BE CONDUCTED |
| ONLY WHEN NOT IN USE. |
| 25.1.12.3 FIRE EXTINGUISHERS. A MINIMUM OF ONE PORTABLE |
| FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN |
| 2-A:10-B:C SHALL BE PROVIDED. |
| |
| |
| |
| |
| 3) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE |
| BELOW NOTED CODE. |
| |
| 14.14 MARKING OF MEANS OF EGRESS. |
| 14.14.1 GENERAL. |
| 14.14.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| MARKED IN ACCORDANCE WITH SECTION 14.14 WHERE REQUIRED |
| IN CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:7.10.1.1] |
| 14.14.1.2 EXITS. |
| 14.14.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, |
| SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY |
| VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. |
| [101:7.10.1.2.1] |
| |
| |
| |
| 4) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE |
| BELOW NOTED CODE. |
| |
| |
| 14.13 EMERGENCY LIGHTING. |
| 14.13.1 GENERAL. |
| 14.13.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| 14.13 FOR THE FOLLOWING: |
| (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| 11 THROUGH 43 OF NFPA 101 |
| |
| |
| |
| 5) PLEASE PROVIDE THE LOCATION OF POWER CORDS/CABLES |
| AND HOW THEY WILL BE PROTECTED FROM DAMAGE AND/OR |
| PEDESTRIAN TRAFFIC. |
| |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |