Plan Review Notes
Plan Review Notes For Permit 16120773
Permit Number 16120773
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-12-30 16:47:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) FINAL APPROVAL IS PENDING SITE FIRE INSPECTIONS AND
 VERIFICATION AS NECASSARY PRIOR TO EVENT START.
2016-12-27 09:13:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE LOCATION OF THE GENERATORS DO NOT INDICATE ANY
 SEPARATION DIMENSIONS OR EXHAUST LOCATIONS. PLEASE
 PROVIDE THEM SHOWING COMPLOIANCE WITH THE BELOW NOTED
 CODE.
  
 11.7 STATIONARY GENERATORS AND STANDBY POWER SYSTEMS.
 11.7.1 STATIONARY COMBUSTION ENGINES AND GAS TURBINES
 INSTALLATION. STATIONARY GENERATOR SETS SHALL BE
 INSTALLED IN ACCORDANCE WITH NFPA 37, STANDARD FOR THE
 INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES
 AND GAS TURBINES, AND NFPA 70.
  
 11.7.2.2 PORTABLE GENERATORS SHALL BE POSITIONED SO
 THAT THE EXHAUST IS DIRECTED AS FOLLOWS:
 (1) AT LEAST 5 FT (1.5 M) IN ANY DIRECTION AWAY FROM
 ANY OPENINGS OR AIR INTAKES
 (2) AWAY FROM THE BUILDING
  
  
  
 2) A 1,000 KW GENERATOR IS LOCATED NEXT TO THE TENT.
 PLEASE SEPARATE AND PROVIDE THE REQUIRED MINIMUM
 DIMENSION NOTED BELOW AND FUEL CAPACITY AND TIME ON THE
 PLAN.
  
 25.1.12 GENERATORS.
 25.1.12.1 GENERATORS AND OTHER INTERNAL COMBUSTION
 POWER SOURCES SHALL BE SEPARATED FROM TEMPORARY
 MEMBRANE STRUCTURES AND TENTS BY A MINIMUM OF 5 FT (1.5
 M) AND SHALL BE PROTECTED FROM CONTACT BY FENCING,
 ENCLOSURE, OR OTHER APPROVED MEANS.
 25.1.12.2 FUELING. FUEL TANKS SHALL BE OF ADEQUATE
 CAPACITY TO PERMIT UNINTERRUPTED OPERATION DURING
 NORMAL OPERATING HOURS. REFUELING SHALL BE CONDUCTED
 ONLY WHEN NOT IN USE.
 25.1.12.3 FIRE EXTINGUISHERS. A MINIMUM OF ONE PORTABLE
 FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN
 2-A:10-B:C SHALL BE PROVIDED.
  
  
  
  
 3) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE
 BELOW NOTED CODE.
  
 14.14 MARKING OF MEANS OF EGRESS.
 14.14.1 GENERAL.
 14.14.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCORDANCE WITH SECTION 14.14 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 43 OF NFPA 101. [101:7.10.1.1]
 14.14.1.2 EXITS.
 14.14.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 [101:7.10.1.2.1]
  
  
  
 4) PLEASE INDICATE WITH A NOTE COMPLIANCE WITH THE
 BELOW NOTED CODE.
  
  
 14.13 EMERGENCY LIGHTING.
 14.13.1 GENERAL.
 14.13.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 14.13 FOR THE FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43 OF NFPA 101
  
  
  
 5) PLEASE PROVIDE THE LOCATION OF POWER CORDS/CABLES
 AND HOW THEY WILL BE PROTECTED FROM DAMAGE AND/OR
 PEDESTRIAN TRAFFIC.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  