Plan Review Notes
Plan Review Notes For Permit 16120762
Permit Number 16120762
Review Stop G
Sequence Number 1
Notes
Date Text
2016-12-22 06:10:17THERE ARE TWO SEPARATE APPLICATIONS THAT HAVE BEEN
 SUBMITTED THAT DO NOT MAKE ANY SENSE. ONE APPLICATION
 IS FOR A GAS LINE TO A KITCHEN STOVE AND THEN A
 SEPARATE APPLICATION FOR THE GAS WATER HEATER.HERE IS
 THE PROCESS:
 1) SUBMIT ONE APPLICATION FOR THE GAS THAT DESCRIBES
 ALL THE GAS WORK TO BE DONE AND LISTS ALL THE GAS
 APPLIANCES TO BE INSTALLED.
 2) SUBMIT A SECOND APPLICATION FOR ANY PLUMBING WORK TO
 BE DONE ( SUCH AS THE WATER PIPING FOR A TANKLESS WATER
 HEATER).
 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2014
 FBC-FUEL GAS SEC.402.4.1 OR 2014 FBC-RES. SEC. G
 2413.3.
 4) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. IF THE
 STOVE IS EXISTING, INDICATE SO ON THE PLANS. IF NEW,
 SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS SHOWING
 IT IS LISTED AND LABELED.
 6) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
 7) . SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.SUBMIT A COPY OF THE PAGE
 FROM THE INSTALLATION MANUAL SHOWING THE REQUIRED
 DISTANCES.
 8) A SEPARATE PERMIT IS REQUIRED FOR ANY ELECTRIC WORK
 TO BE DONE.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  