Plan Review Notes For Permit 16120759 |
Permit Number |
16120759 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-22 06:30:48 | 1) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE | | DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS | | OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE | | THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC | | SEC.402.3, FBCR SEC. G 2413.3. I CANNOT BEGIN TO REVIEW | | THE PLAN UNLESS I KNOW WHAT SIZING TABLE IS BEING USED. | | 2) IS THE RANGE IN THE MAIN HOUSE NEW OR EXISTING? | | INDICATE SUCH ON THE PLAN. IF IT IS NEW, SUBMIT THE | | MANUFACTURER'S SPECIFICATION SHEETS FOR THE UNIT. | | 3) WHAT TYPE OF GAS PIPE IS SUPPLYING THE RANGE? | | 4) SHOW THE LOCATION OF ANY OPERABLE DOORS OR WINDOWS | | IN PROXIMITY TO THE TANKLESS WATER HEATER. THE LOCATION | | OF THE WATER HEATER SHALL COMPLY WITH THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS. SUBMIT A COPY | | OF THE PAGE FROM THE INSTALLATION MANUAL SHOWING THE | | REQUIRED DISTANCES FROM ANY OPEERABLE DOORS AND | | WINDOWS. | | 5) WHERE IS THE WATER SUPPLY LINE TO THE TANKLESS WATER | | HEATER COMING FROM AND WHERE IS THE HOT WATER SUPPLY | | LINE GOING TO ? SHOW THE LOCATION OF THESE LINES ON THE | | PLAN. WPB AMEND. FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|