Plan Review Notes For Permit 16120735 |
Permit Number |
16120735 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-21 14:32:38 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- PROVIDE CURRENT REVISED FLORIDA PRODUCT APPROVAL FOR | | ROOF TILES AND ROOF TILE UNDERLAYMENT SUBMITTED. FAC | | 61G20-3.002(33). | | | | 2- SPECIFY ROOF TILE FASTENING METHOD TO VERIFY DESIGN | | PRESSURES. SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION | | (2014) | | | | 3- FLAT ROOF NOA 12-1003.05 SUBMITTED: | | A) SPECIFY ASSEMBLY TO BE INSTALLED. SEC. R301.1 | | FBC-RESIDENTIAL. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS. SEC. | | R301.1 FBC-RESIDENTIAL. | | | | 4- VALUATION LOW. PROVIDE COPY OF SIGNED CONTRACT. SEC. | | 109.3 CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|