Plan Review Notes For Permit 16120700 |
Permit Number |
16120700 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-21 06:21:29 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PLEASE CLARIFY SCOPE OF WORK. NEW 220VOLT LOAD ARE | | INDICATE ON SKETCH SUBMITTED. SHOWING NEW LIGHTING AND | | RECEPTACLE OUTLETS. PROVIDE REVISED LOADS CALCULATION | | FOR THE PANEL WHERE THESE BRANCH CIRCUIT ORIGINATE. | | 2. PER WPB AMENDMENTS, PROVIDE A DRAWING THAT IS CLEAR, | | SCALED AND EVIDENT AS TO SCOPE OF WORK. DRAWINGS SHOULD | | BE PER FBC 107.2.1; (INFORMATION ON CONSTRUCTION | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | MATERIAL. ALSO SHALL BE OF SUFFICIENT CLARITY TO | | INDICATE THE LOCATION, NATURE AND EXTENT OF WORK | | PROPOSED. SHOW IN DETAIL THAT IT WILL CONFORM TO CODE. | | 3. A COMPLETE REVIEW COULD NOT BE PERFORMED DUE TO | | SKETCH SUBMITTED. | | 4. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS OR CONCERNS. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | |
|