Plan Review Notes For Permit 16120671 |
Permit Number |
16120671 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-12-22 11:38:45 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) SHEET LS101 - THERE ARE REVISION CLOUDS INDICATED AS | | # 5; HOWEVER, THERE IS NOT NOTE OF SYMBOL INDICATOR AS | | TO WHAT THE REVISION IS. | | | | PLEASE IDENTIFY WHAT THE REVISON IS AND ITS FUNCTION. | | | | | | | | | | 2) SHEET AE412 - THERE IS A REVISION CLOUD INDICATING A | | FABRIC COVERED PANEL SECURED TO THE WALL. THERE ARE NO | | MANUFUACTURES SPEC/PRODUCT SHEETS PROVIDED IDENTIFYING | | ANY FIRE RETARDENT - FLAME SPREAD - SMOKE TOXICITY. | | | | PLEASE PROVIDE ALL APPLICABLE PRODUCTS SPECIFICATION | | SHEETS FOR THE RECORD AND ALSO TO ENSURE FIRE CODE | | COMPLIANCE. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|