2017-01-06 08:08:02 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16120671 |
| W. P. B. PERMIT: 16050249 |
| ADD: 3501 PARKER AVE. |
| CONT: HEDRICK BROTHERS |
| TEL: 561-324-1127 |
| E-MAIL: |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JAN. 06/ 2017 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A NARRATIVE DESCRIBING WHAT REVISION |
| # 5 IS. |
| EXAMPLES LS101 VERSES AE111. AE111 SHOWS A REVISION # 5 |
| IN THE WET ROOM 165B WHEREAS LS101 DOESN?T. ON THE SAME |
| TWO SHEETS ON SHEET LS101 IN THE SAME AREA CORRIDOR 164 |
| THERE IS A REVISION # 5 IT APPEARS TO BE A DIMENSION |
| LINE TO THE CENTERLINE OF AN FEC (FIRE EXTINGUISHER IN |
| CABINET). 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| ANOTHER AREA OF QUESTION IS FOUND ON SHEET AE112 |
| REVISION # 5 STORAGE ROOM 124 & CORRIDOR 130, THE |
| REVISION APPEARS TO BE THE SAME AS REVISION # 4. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| |
| 2) SHEET AE320 REVISION # 5; |
| 2A) WALL SECTION # 1 SHOWS A ROOF TOP REVISION TO |
| LIGHTWEIGHT CONCRETE R-20 MIN. AT LOW POINT, ON |
| CORRUGATED STEEL DECK. WILL REQUIRE A CHANGE OF ROOFING |
| ASSEMBLIES PRODUCT APPROVALS, AND BE REVIEWED BY THE |
| DESIGNER OF RECORD BEFORE SUBMITTING TO THE BUILDING |
| DEPARTMENT. |
| FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.? |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, |
| |
| 2B) WALL SECTION # 2 SHOWS FABRIC COVERED ACOUSTIC |
| PANELS MECHANICALLY ANCHORED TO WALL/ SOLID BLOCKING |
| PER MANUFACTURERS SPECIFICATION. TO DATE THERE HAS BEEN |
| NO PRODUCT DATA SHEETS SHOWING COMPLIANCE OF MATERIALS |
| FOR THE FABRIC OR ACOUSTICAL PANELS. |
| PLEASE SHOW COMPLIANCE WITH 803.5 TEXTILE WALL |
| COVERINGS. WHERE USED AS INTERIOR WALL FINISH |
| MATERIALS, TEXTILE WALL COVERINGS, INCLUDING MATERIALS |
| HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, LOOPED OR |
| SIMILAR SURFACE AND CARPET AND SIMILAR TEXTILE |
| MATERIALS, SHALL BE TESTED IN THE MANNER INTENDED FOR |
| USE, USING THE PRODUCT MOUNTING SYSTEM, INCLUDING |
| ADHESIVE, AND SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTION 803.1.2, 803.1.3 OR 803.1.4. |
| |
| ACOUSTICAL PANELS: PLEASE PROVIDE THE MANUFACTURERS |
| SPEC FOR INSTALLATION AND COMPLIANCE WITH FBC-B TABLE |
| 803.9 INTERIOR WALL AND CEILING FINISHES REQUIRED BY |
| OCCUPANCY. MOUNTING DETAILS ARE LOCATED DETAIL 5 SHEET |
| AE 712. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |